Reference Source

Industrial VFD fault and alarm codes by brand

What the fault and alarm codes on the display of an industrial variable-frequency drive (VFD) stand for, taken from each manufacturer's own manual. Codes are short strings that look alike across brands and mean different things: 13 is over current on a Danfoss VLT and a ground fault on an Allen-Bradley PowerFlex 40. Each record gives the code exactly as the keypad shows it, the name the manual prints beside it, and — where the manual grades events — whether it is a warning the drive keeps running through or a fault that trips it. Where the manual's own troubleshooting table states a cause and a corrective action for the code, those are carried too; where it doesn't, the linked manual page is the place to check.

Records340
Sources3
Verified
Review by
Licencefactual compilation from manufacturer technical manuals

The data

Fault codeBrandModel / seriesFault nameTypeCauseCorrective action
14DanfossFC 301/302Earth (ground) faultALARMThere is current from the output phase-to-ground, either in the cable between the frequency converter and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the frequency converter and current going into the frequency converter from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the frequency converter must be the same as the current going into the frequency converter.• Remove power to the frequency converter and repair the ground fault. • Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. • Reset any potential individual offset in the 3 current transducers in the frequency converter. Perform the manual initialization or perform a complete AMA. This method is most relevant after changing the power card.
15DanfossFC 301/302Hardware mismatchALARMA fitted option is not operational with the present control card hardware or software. Record the value of the following parameters and contact Danfoss. • Parameter 15-40 FC Type. • Parameter 15-41 Power Section. • Parameter 15-42 Voltage. • Parameter 15-43 Software Version. • Parameter 15-45 Actual Typecode String. • Parameter 15-49 SW ID Control Card. • Parameter 15-50 SW ID Power Card. • Parameter 15-60 Option Mounted. • Parameter 15-61 Option SW Version (for each option slot).
16DanfossFC 301/302Short circuitALARMThere is short-circuiting in the motor or motor wiring.• Remove the power to the frequency converter and repair the short circuit. WARNING HIGH VOLTAGE Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use qualified personnel to install, start up, and maintain the frequency converter can result in death or serious injury. • Disconnect power before proceeding.
29DanfossFC 301/302Heat Sink tempALARMThe maximum temperature of the heat sink is exceeded. The temperature fault is not reset until the temperature drops below a defined heat sink temperature. The trip and reset points are different based on the frequency converter power size.Check for the following conditions: • The ambient temperature is too high. • The motor cables are too long. • Incorrect airflow clearance above and below the frequency converter. • Blocked airflow around the frequency converter. • Damaged heat sink fan. • Dirty heat sink.
30DanfossFC 301/302Motor phase U missingALARM
31DanfossFC 301/302Motor phase V missingALARMMotor phase V between the frequency converter and the motor is missing. WARNING HIGH VOLTAGE Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use qualified personnel to install, start up, and maintain the frequency converter can result in death or serious injury. • Disconnect power before proceeding.• Remove the power from the frequency converter and check motor phase V.
32DanfossFC 301/302Motor phase W missingALARMMotor phase W between the frequency converter and the motor is missing. WARNING HIGH VOLTAGE Frequency converters contain high voltage when connected to AC mains input, DC supply, or load sharing. Failure to use qualified personnel to install, start up, and maintain the frequency converter can result in death or serious injury. • Disconnect power before proceeding.• Remove the power from the frequency converter and check motor phase W.
33DanfossFC 301/302Inrush faultALARMToo many power-ups have occurred within a short time period.• Let the unit cool to operating temperature.
37DanfossFC 301/302Phase imbalanceALARMThere is a current imbalance between the power units.
38DanfossFC 301/302Internal faultALARM
39DanfossFC 301/302Heat sink sensorALARMNo feedback from the heat sink temperature sensor. The signal from the IGBT thermal sensor is not available on the power card. The problem could be on the power card, on the gatedrive card, or the ribbon cable between the power card and gatedrive card.
43DanfossFC 301/302Ext. supplyALARMVLT® Extended Relay Option MCB 113 is mounted without external 24 V DC. Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle.
45DanfossFC 301/302Earth fault 2ALARMGround fault.• Check for proper grounding and loose connections. • Check for proper wire size. • Check the motor cables for short circuits or leakage currents.
46DanfossFC 301/302Power card supplyALARMThe supply on the power card is out of range. Another reason can be a defective heat sink fan. There are 3 supplies generated by the switch mode supply (SMPS) on the power card: • 24 V. • 5 V. • ±18 V. When powered with VLT® 24 V DC Supply MCB 107, only the 24 V and 5 V supplies are monitored. When powered with 3-phase mains voltage, all 3 supplies are monitored.• Check for a defective power card. • Check for a defective control card. • Check for a defective option card. • If a 24 V DC supply is used, verify proper supply power. • Check for a defective heat sink fan.
50DanfossFC 301/302AMA calibration failedALARMContact the Danfoss supplier or Danfoss service department.
51DanfossFC 301/302AMA check Unom and InomALARMThe settings for motor voltage, motor current, and motor power are wrong.• Check the settings in parameters 1-20 to 1-25.
52DanfossFC 301/302AMA low InomALARMThe motor current is too low.• Check the settings in parameter 1-24 Motor Current.
53DanfossFC 301/302AMA motor too bigALARMThe motor is too large for the AMA to operate.
54DanfossFC 301/302AMA motor too smallALARMThe motor is too small for the AMA to operate.
55DanfossFC 301/302AMA parameter out of rangeALARMThe AMA cannot run because the parameter values of the motor are outside of the acceptable range.
56DanfossFC 301/302AMA interrupted by userALARMThe AMA is manually interrupted.
57DanfossFC 301/302AMA internal faultALARMTry to restart the AMA. Repeated restarts can overheat the motor.
58DanfossFC 301/302AMA Internal faultALARMContact the Danfoss supplier.
63DanfossFC 301/302Mechanical brake lowALARMThe actual motor current has not exceeded the release brake current within the start delay time window.
67DanfossFC 301/302Option module configuration has changedALARMOne or more options have either been added or removed since the last power-down. Check that the configuration change is intentional and reset the unit.
68DanfossFC 301/302Safe Stop activatedALARMSafe Torque Off (STO) has been activated. To resume normal operation, apply 24 V DC to terminal 37, then send a reset signal (via bus, digital I/O, or by pressing [Reset]).
69DanfossFC 301/302Power card temperatureALARMThe temperature sensor on the power card is either too hot or too cold.• Check that the ambient operating temperature is within limits. • Check for clogged filters. • Check fan operation. • Check the power card.
70DanfossFC 301/302Illegal FC configurationALARMThe control card and power card are incompatible. To check compatibility, contact the Danfoss supplier with the type code from the unit nameplate and the part numbers of the cards.
71DanfossFC 301/302PTC 1 safe stopALARMSTO has been activated from the VLT® PTC Thermistor Card MCB 112 (motor too warm). Normal operation can be resumed when the MCB 112 applies 24 V DC to terminal 37 again (when the motor temperature reaches an acceptable level), and when the digital input from the MCB 112 is deactivated. When that happens, send a reset signal (via bus or digital I/O, or press [Reset]).
72DanfossFC 301/302Dangerous failureALARMSTO with trip lock. An unexpected combination of STO commands has occurred: • VLT® PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled. • MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 1 warning in parameter 5-19 Terminal 37 Safe Stop), STO is activated, and X44/10 is not activated.
74DanfossFC 301/302PTC ThermistorALARMAlarm related to VLT® PTC Thermistor Card MCB 112. The PTC is not working.
75DanfossFC 301/302Illegal profile sel.ALARMDo not write the parameter value while the motor is running. Stop the motor before writing the MCO profile to parameter 8-10 Control Word Profile.
78DanfossFC 301/302Tracking errorALARMThe difference between setpoint value and actual value exceeds the value in parameter 4-35 Tracking Error.• Disable the function or select an alarm/warning in parameter 4-34 Tracking Error Function. • Investigate the mechanics around the load and motor. Check feedback connections from motor encoder to frequency converter. • Select motor feedback function in parameter 4-30 Motor Feedback Loss Function. • Adjust the tracking error band in parameter 4-35 Tracking Error and parameter 4-37 Tracking Error Ramping.
79DanfossFC 301/302Illegal power section configurationALARMThe scaling card has an incorrect part number or is not installed. The MK102 connector on the power card could not be installed.
80DanfossFC 301/302Drive initializedALARMParameter settings are initialized to default settings after a manual reset. To clear the alarm, reset the unit.
81DanfossFC 301/302CSIV corruptALARMCSIV file has syntax errors.
82DanfossFC 301/302CSIV parameter errorALARMCSIV failed to initialize a parameter.
83DanfossFC 301/302Illegal option combinationALARMThe mounted options are incompatible.
84DanfossFC 301/302No safety optionALARMThe safety option was removed without applying a general reset. Reconnect the safety option.
88DanfossFC 301/302Option detectionALARMA change in the option layout is detected. Parameter 14-89 Option Detection is set to [0] Frozen config- uration and the option layout has been changed. • To apply the change, enable option layout changes in parameter 14-89 Option Detection. • Alternatively, restore the correct option configu- ration.
90DanfossFC 301/302Feedback monitorALARMCheck the connection to encoder/resolver option and, if necessary, replace VLT® Encoder Input MCB 102 or VLT® Resolver Input MCB 103.
91DanfossFC 301/302Analog input 54 wrong settingsALARMSet switch S202 in position OFF (voltage input) when a KTY sensor is connected to analog input terminal 54.
99DanfossFC 301/302Locked rotorALARMThe rotor is blocked.
164DanfossFC 301/302ATEX ETR cur.lim.alarmALARMOperating above the characteristic curve for more than 60 s within a period of 600 s activates the alarm, and the frequency converter trips.
166DanfossFC 301/302ATEX ETR freq.lim.alarmALARMThe frequency converter has operated for more than 60 s (in a period of 600 s) below the allowed minimum frequency (parameter 1-98 ATEX ETR interpol. points freq.).
213DanfossFC 301/302Homing timeoutALARMHoming was started but did not finish within the time defined in parameter 17-85 Homing Timout.
214DanfossFC 301/302No sensor inputALARMA homing process with a homing function that requires a sensor, or touch probe positioning is started with no input defined for the sensor.
246DanfossFC 301/302Power card supplyALARMThis alarm is only for enclosure size F frequency converters. It is equivalent to alarm 46, Power card supply. The report value in the alarm log indicates which power module generated the alarm: 1 = Inverter module to the far left. 2 = Middle inverter module in F2 or F4 frequency converter. 2 = Right inverter module in F1 or F3 frequency converter. 3 = Right inverter module in F2 or F4 frequency converter. 5 = Rectifier module.
430DanfossFC 301/302PWM DisabledALARMThe PWM on the power card is disabled.
AErYaskawaGA800Station Address Setting ErrorAlarm
bATYaskawaGA800Keypad Battery Low VoltageAlarmThe keypad battery voltage is low.Replace the keypad battery.
bbYaskawaGA800BaseblockAlarmAn external baseblock command was entered through one of the MFDI terminals Sx, and the drive output stopped as shown by an external baseblock command.Examine the external sequence and timing of the baseblock command input.
bCEYaskawaGA800Bluetooth Communication ErrorAlarmThe smartphone or tablet with DriveWizard Mobile or DriveWizard installed is too far from the keypad.Use the smartphone or tablet 10 m (32.8 ft) or nearer to the keypad.
boLYaskawaGA800Braking Transistor OverloadAlarmThe duty cycle of the braking transistor is high (the regeneration power or repetition frequency is high).• Install a braking unit (CDBR-series). • Install a regenerative converter. • Increase the deceleration time.
bUSYaskawaGA800Option Communication ErrorAlarm
CALLYaskawaGA800Serial Comm Transmission ErrorAlarmThe communications cable wiring is incorrect.Correct wiring errors.
CEYaskawaGA800Modbus Communication ErrorAlarmThe communications cable wiring is incorrect.Correct wiring errors.
CP1YaskawaGA800Comparator 1 Limit ErrorAlarmThe monitor value set in H2-20 [Comparator 1 Monitor Selection] was in the range of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit].Examine the monitor value and remove the cause of the fault.
CP2YaskawaGA800Comparator 2 Limit ErrorAlarmThe monitor value set in H2-26 [Comparator 2 Monitor Selection] was outside the range of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit].Examine the monitor value and remove the cause of the fault.
CyCYaskawaGA800MECHATROLINK CommCycleSettingErrAlarmThe communications cycle setting of the controller is not in the permitted range of the MECHATROLINK interface option.Set the communications cycle of the controller in the permitted range of the MECHATROLINK interface option.
CyPoYaskawaGA800Cycle Power to Accept ChangesAlarm
dEvYaskawaGA800Speed DeviationAlarmThe load is too heavy.Decrease the load.
dnEYaskawaGA800Drive DisabledAlarmA terminal set for H1-xx = 6A [Drive Enable] turned OFF.Examine the operation sequence.
dWA2YaskawaGA800DriveWorksEZ Alarm 2AlarmThere was an error in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the error.
dWA3YaskawaGA800DriveWorksEZ Alarm 3AlarmThere was an error in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the error.
dWALYaskawaGA800DriveWorksEZ AlarmAlarmThere was an error in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the error.
E5YaskawaGA800MECHATROLINK Watchdog Timer ErrAlarmThe drive detected a watchdog circuit exception while it received data from the controller.Examine the MECHATROLINK cable connection.
EFYaskawaGA800FWD/REV Run Command Input ErrorAlarmA forward command and a reverse command were input at the same time for longer than 0.5 s.Examine the forward and reverse command sequence and correct the problem.
EF0YaskawaGA800Option Card External FaultAlarmThe communication option received an external fault from the controller.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input from the controller.
EF1YaskawaGA800External Fault (Terminal S1)AlarmMFDI terminal S1 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF2YaskawaGA800External Fault (Terminal S2)AlarmMFDI terminal S2 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF3YaskawaGA800External Fault (Terminal S3)AlarmMFDI terminal S3 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF4YaskawaGA800External Fault (Terminal S4)AlarmMFDI terminal S4 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF5YaskawaGA800External Fault (Terminal S5)AlarmMFDI terminal S5 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF6YaskawaGA800External Fault (Terminal S6)AlarmMFDI terminal S6 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF7YaskawaGA800External Fault (Terminal S7)AlarmMFDI terminal S7 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF8YaskawaGA800External Fault (Terminal S8)AlarmMFDI terminal S8 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EP24vYaskawaGA800External Power 24V SupplyAlarmThe voltage of the main circuit power supply decreased, and the 24 V power supply is supplying power to the drive.• Examine the main circuit power supply. • Turn ON the main circuit power supply to run the drive.
FAnYaskawaGA800Internal Fan FaultAlarmThe circulation fan stopped operating correctly.• Examine circulation fan operation. • Re-energize the drive. • Examine U4-03 [Cooling Fan Ope Time] and U4-04 [Cool Fan Maintenance]. If there is damage to the circulation fan or if the performance life of the fan is expired, replace the fan.
FbHYaskawaGA800Excessive PID FeedbackAlarmThe FbH detection level is set incorrectly.Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID High Feedback Detection Time].
FbLYaskawaGA800PID Feedback LossAlarmThe FbL detection level is set incorrectly.Adjust b5-13 [PID Feedback Loss Detection Lvl] and b5-14 [PID Feedback Loss Detection Time].
L24vYaskawaGA800Loss of External Power 24 SupplyAlarm
LoGYaskawaGA800Log Com ErrorAlarm
LT-1YaskawaGA800Cooling Fan Maintenance TimeAlarmThe cooling fan is at 90% of its expected performance life.1. Replace the cooling fan. 2. Set o4-03 = 0 [Fan Operation Time Setting = 0 h] to reset the cooling fan operation time.
LT-2YaskawaGA800Capacitor Maintenance TimeAlarmThe capacitors for the main circuit and control circuit are at 90% of expected performance life.Replace the control board or the drive.
LT-3YaskawaGA800SoftChargeBypassRelay MainteTimeAlarmThe soft charge bypass relay is at 90% of its expected performance life.Replace the control board or the drive.
LT-4YaskawaGA800IGBT Maintenance Time (50%)AlarmThe IGBT is at 50% of its expected performance life.Check the load, carrier frequency, and output frequency.
oHYaskawaGA800Heatsink OverheatAlarmThe ambient temperature is high and the heatsink temperature of the drive is more than the value set in L8-02 [Overheat Alarm Level].• Measure the ambient temperature. • Increase the airflow in the control panel. • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature. • Remove objects near the drive that are producing too much heat.
oH2YaskawaGA800External Overheat (H1-XX=B)Alarm
oH3YaskawaGA800Motor Overheat (PTC Input)AlarmThe thermistor wiring that detects motor temperature is defective.Correct wiring errors.
oL3YaskawaGA800Overtorque 1Alarm
oL4YaskawaGA800Overtorque 2Alarm
oL5YaskawaGA800Mechanical Weakening Detection 1AlarmThe drive detected overtorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select].Do a deterioration diagnostic test on the machine side.
oSYaskawaGA800OverspeedAlarmThere is overshoot.• Decrease C5-01 [ASR Proportional Gain 1] and increase C5-02 [ASR Integral Time 1]. • Adjust the pulse train gain with H6-02 to H6-05 [Pulse Train Input Setting Parameters].
ovYaskawaGA800DC Bus OvervoltageAlarmThe deceleration time is too short and too much regenerative energy is flowing back into the drive.1. Set L3-04 = 1 [Stall Prevention during Decel = General Purpose]. 2. Increase the values set in C1-02, C1-04, C1-06, or C1-08 [Deceleration Times]. 3. Connect a dynamic braking option to the drive. 4. Perform Deceleration Rate Tuning.
PFYaskawaGA800Input Phase LossAlarmThere is a phase loss in the drive input power.Correct errors with the wiring for main circuit drive input power.
PGoYaskawaGA800Encoder (PG) Feedback LossAlarmThe encoder cable is disconnected or wired incorrectly.Examine for wiring errors or disconnected wires in the encoder cable, and repair problems.
PGoHYaskawaGA800Encoder (PG) Hardware FaultAlarmThe encoder cable is disconnected.Correct any disconnected wires in the encoder cable.
rUnYaskawaGA800Motor Switch during RunAlarmThe drive received a Motor 2 Selection [H1-xx = 16] during run.Make sure that the drive receives the Motor 2 Selection while the drive is stopped.
SEYaskawaGA800Modbus Test Mode ErrorAlarmMEMOBUS/Modbus communications self- diagnostics [H1-xx = 67] was done while the drive was running.Stop the drive and do MEMOBUS/Modbus communications self- diagnostics.
SToYaskawaGA800Safe Torque OFFAlarmSafe Disable inputs H1-HC and H2-HC are open.• Make sure that the Safe Disable signal is input from an external source to terminal H1-HC and H2-HC. • When the Safe Disable function is not in use, use a jumper to connect terminals H1-HC and H2-HC.
SToFYaskawaGA800Safe Torque OFFAlarm
TiMYaskawaGA800Keypad Time Not SetAlarmThere is a battery in the keypad, but the date and time are not set.Use the keypad to set the date and time.
TrPCYaskawaGA800IGBT Maintenance Time (90%)AlarmThe IGBT is at 90% of its expected performance life.Replace the IGBTor the drive.
UL3YaskawaGA800Undertorque Detection 1Alarm
UL4YaskawaGA800Undertorque Detection 2Alarm
UL5YaskawaGA800Mechanical Weakening Detection 2AlarmThe drive detected undertorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select].Examine the machine for deterioration.
UvYaskawaGA800UndervoltageAlarmThe drive input power voltage is changing too much.• Examine the input power for problems. • Make the drive input power stable. • If the input power supply is good, examine the magnetic contactor on the main circuit side for problems.
End1YaskawaGA800Excessive Rated Voltage SettingAuto-Tuning ErrorThe torque reference was more than 20% during Auto-Tuning or the no-load current that was measured after Auto-Tuning is more than 80%.• Make sure that the input motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data. • If you can uncouple the motor and load, remove the motor from the machine and do Rotational Auto-Tuning again. • If you cannot uncouple the motor and load, use the results from Auto-Tuning.
End2YaskawaGA800Iron Core Saturation CoefficientAuto-Tuning ErrorThe motor nameplate data entered during Auto- Tuning is incorrect.• Make sure that the input motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data.
End3YaskawaGA800Rated Current Setting AlarmAuto-Tuning ErrorThe rated current value is incorrect.Do Auto-Tuning again and set the correct rated current shown on the motor nameplate.
End4YaskawaGA800Adjusted Slip Calculation ErrorAuto-Tuning Error
End5YaskawaGA800Resistance Tuning ErrorAuto-Tuning ErrorThe Auto-Tuning results of the Line-to-Line Resistance were not in the applicable range.• Make sure that the input motor nameplate data is correct. • Examine and repair damaged motor wiring.
End6YaskawaGA800Leakage Inductance AlarmAuto-Tuning ErrorThe Auto-Tuning results were not in the applicable parameter setting range.Make sure that the input motor nameplate data is correct, and do Auto-Tuning again.
End7YaskawaGA800No-Load Current AlarmAuto-Tuning ErrorThe Auto-Tuning results of the motor no-load current value were not in the applicable range.Examine and repair damaged motor wiring.
End8YaskawaGA800HFI AlarmAuto-Tuning Error
End9YaskawaGA800Initial Pole Detection AlarmAuto-Tuning ErrorThe drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning.• Set the correct value on the motor nameplate E5-xx [PM motor parameters] or do Stationary/Rotational Auto-Tuning, and then do High Frequency Injection Tuning again. • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled], make sure that the motor does not rotate in reverse at start.
Er-01YaskawaGA800Motor Data ErrorAuto-Tuning ErrorThe motor nameplate data entered during Auto- Tuning is incorrect.• Make sure that the motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data.
Er-02YaskawaGA800Drive in an Alarm StateAuto-Tuning ErrorThe motor nameplate data entered during Auto- Tuning is incorrect.• Make sure that the motor nameplate data entered in Auto-Tuning is correct. • Do Auto-Tuning again and correctly set the motor nameplate data.
Er-03YaskawaGA800STOP Button was PressedAuto-Tuning Error
Er-04YaskawaGA800Line-to-Line Resistance ErrorAuto-Tuning Error
Er-05YaskawaGA800No-Load Current ErrorAuto-Tuning Error
Er-08YaskawaGA800Rated Slip ErrorAuto-Tuning ErrorThe motor nameplate data entered during Auto- Tuning is incorrect.• Make sure that the input motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data.
Er-09YaskawaGA800Acceleration ErrorAuto-Tuning ErrorThe motor did not accelerate for the specified acceleration time.1. Increase the value set in C1-01 [Acceleration Time 1]. 2. Disconnect the machine from the motor and do Rotational Auto-Tuning again.
Er-10YaskawaGA800Motor Direction ErrorAuto-Tuning ErrorThere is defective drive and motor wiring.Examine and repair motor wiring.
Er-11YaskawaGA800Motor Speed ErrorAuto-Tuning ErrorThe torque reference during acceleration is too high (100%).• Increase the value set in C1-01 [Acceleration Time 1]. • Disconnect the machine from the motor and do Rotational Auto- Tuning again.
Er-12YaskawaGA800Current Detection ErrorAuto-Tuning Error
Er-13YaskawaGA800Leakage Inductance ErrorAuto-Tuning Error
Er-14YaskawaGA800Motor Speed Error 2Auto-Tuning ErrorThe motor speed was more than two times the amplitude of speed reference during Inertia Tuning.Decrease the value set in C5-01 [ASR Proportional Gain 1].
Er-15YaskawaGA800Torque Saturation ErrorAuto-Tuning ErrorDuring Inertia Tuning, the output torque was more than the value set in L7-01 to L7-04 [Torque Limit].• Increase the value set in L7-01 to L7-04 [Torque Limit] as much as possible. • Decrease the values set for the frequency and amplitude of the test signals used when doing inertia tuning. First, decrease the test signal amplitude, and then do Inertia Tuning. If the error continues, decrease the test signal frequency and do Inertia Tuning again.
Er-16YaskawaGA800Inertia ID ErrorAuto-Tuning ErrorThe inertia found by the drive was too small or too large during Inertia Tuning (10% or less, or 50000% or more).• Decrease the values set for the frequency and amplitude of the test signals used when doing inertia tuning. First, decrease the test signal amplitude, and then do Inertia Tuning. If the error continues, decrease the test signal frequency and do Inertia Tuning again. • Correctly set the motor inertia as specified by the motor, and do Inertia Tuning again.
Er-17YaskawaGA800Reverse Prohibited ErrorAuto-Tuning Error
Er-18YaskawaGA800Back EMF ErrorAuto-Tuning ErrorThe result of the induced voltage tuning was not in the applicable range.1. Make sure that the input motor nameplate data is correct. 2. Do Auto-Tuning again and correctly set the motor nameplate data.
Er-19YaskawaGA800PM Inductance ErrorAuto-Tuning ErrorThe Auto-Tuning results of the PM motor inductance were not in the applicable range.1. Make sure that the input motor nameplate data is correct. 2. Do Auto-Tuning again and correctly set the motor nameplate data.
Er-20YaskawaGA800Stator Resistance ErrorAuto-Tuning ErrorThe Auto-Tuning results of the PM Motor Stator Resistance were not in the applicable range.1. Make sure that the input motor nameplate data is correct. 2. Do Auto-Tuning again and correctly set the motor nameplate data.
Er-21YaskawaGA800Z Pulse Correction ErrorAuto-Tuning Error
Er-25YaskawaGA800HighFreq Inject Param Tuning ErrAuto-Tuning ErrorThe motor data is incorrect.Do Stationary Auto-Tuning again.
CPyEYaskawaGA800Error Writing DataBackup Function Runtime ErrorParameter restore did not end correctly.Restore the parameters.
CSErYaskawaGA800Control Mode MismatchBackup Function Runtime ErrorThe keypad is broken.Replace the keypad.
dFPSYaskawaGA800Drive Model MismatchBackup Function Runtime ErrorYou tried to restore parameters to a different drive model than the one that you backed up.1. Examine the drive model that you used to back up the parameters. 2. Restore the parameters.
iFErYaskawaGA800Communication ErrBackup Function Runtime Error
ndATYaskawaGA800Model,VolClass,Capacity MismatchBackup Function Runtime Error
PWErYaskawaGA800DWEZ Password MismatchBackup Function Runtime ErrorThe password set in the backup operation with qx-xx [DriveWorksEZ Parameters] and rx-xx [DriveWorksEZ Connections] is incorrect.Set the DWEZ PC software password supplied by Yaskawa for the DWEZ program user ID downloaded to the drive.
rdErYaskawaGA800Error Reading DataBackup Function Runtime Error
vAErYaskawaGA800Voltage Class, Capacity MismatchBackup Function Runtime ErrorThe power supply specifications or drive capacity parameter settings are different between the keypad and the drive.1. Make sure that drive model and the value set in o2-04 [Drive Model (KVA) Selection] agree. 2. Restore the parameters.
vFyEYaskawaGA800Parameters do not MatchBackup Function Runtime ErrorThe parameters that are backed up in the keypad and the parameters in the drive are not the same.1. Restore or backup the parameter again. 2. Verify the parameters.
bATYaskawaGA800Keypad Battery Low VoltageFaultThe keypad battery voltage is low.Replace the keypad battery.
bCEYaskawaGA800Bluetooth Communication FaultFaultThe smartphone or tablet with DriveWizard Mobile or DriveWizard installed is too far from the keypad.Use the smartphone or tablet 10 m (32.8 ft) or nearer to the keypad.
boLYaskawaGA800BrakingTransistor Overload FaultFaultThe duty cycle of the braking transistor is high (the regeneration power or repetition frequency is high).• Install a braking unit (CDBR-series). • Install a regenerative converter. • Increase the deceleration time.
bUSYaskawaGA800Option Communication ErrorFault
CEYaskawaGA800Modbus Communication ErrorFaultThe communications cable wiring is incorrect.Correct wiring errors.
CFYaskawaGA800Control FaultFault
CoFYaskawaGA800Current Offset FaultFaultThe drive starts operation while the induced voltage stays in the motor (during coasting to a stop or after fast deceleration).• Make a sequence that does not restart operation when induced voltage stays in the motor. • Set b3-01 = 1 [Speed Search at Start Selection = Enabled]. • Use Speed Search from Fmax or Fref [H1-xx = 61, 62] to do a speed search through one of the external terminals.
CP1YaskawaGA800Comparator 1 Limit FaultFaultThe monitor value set in H2-20 [Comparator 1 Monitor Selection] was in the range of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit].Examine the monitor value and remove the cause of the fault.
CP2YaskawaGA800Comparator 2 Limit FaultFaultThe monitor value set in H2-26 [Comparator 2 Monitor Selection] was outside the range of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit].Examine the monitor value and remove the cause of the fault.
CPF00YaskawaGA800Control Circuit ErrorFaultA drive hardware problem occurred.• Re-energize the drive. • If the fault stays, replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
CPF01YaskawaGA800Control Circuit ErrorFaultA drive hardware problem occurred.• Re-energize the drive. • If the fault stays, replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
CPF06YaskawaGA800Control Circuit Error (EEPROM Memory Data Error)Fault
CPF24YaskawaGA800Control Circuit Error (Drive Unit Signal Fault)FaultA drive hardware problem occurred.• Re-energize the drive. • If the fault stays, replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
dEvYaskawaGA800Speed DeviationFaultThe load is too heavy.Decrease the load.
dv1YaskawaGA800Z Pulse FaultFault
dv2YaskawaGA800Z Pulse Noise Fault DetectionFault
dv3YaskawaGA800Inversion DetectionFault
dv4YaskawaGA800Inversion Prevention DetectionFaultAn external force on the load side rotated the motor.• Make sure that the motor is rotating in the correct direction. • Find and repair problems on the load side that cause the motor to rotate from the load side. • Disable detection of this fault for applications that rotate the motor from the load side in the opposite direction of the speed reference. The drive will not detect this fault if F1-19 = 0 [Deviation 4 Detection Selection = Disabled].
dv7YaskawaGA800Polarity Judge TimeoutFaultThere is a disconnection in the motor coil winding.Measure the motor line-to-line resistance and replace the motor if a coil is disconnected.
dWF1YaskawaGA800EEPROM Memory DWEZ Data ErrorFaultThere is an error in the EEPROM peripheral circuit.• Re-energize the drive. • If the fault stays, replace the control board or the drive. For information about replacing the control board, contact Yaskawa or your nearest sales representative.
dWF2YaskawaGA800DriveWorksEZ Fault 2FaultThere was a fault in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the fault.
dWF3YaskawaGA800DriveWorksEZ Fault 3FaultThere was a fault in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the fault.
dWFLYaskawaGA800DriveWorksEZ FaultFaultThere was a fault in the DriveWorksEZ program.Examine the DriveWorksEZ program and remove the cause of the fault.
E5YaskawaGA800MECHATROLINK Watchdog Timer ErrFaultThe drive detected a watchdog circuit exception while it received data from the controller.Examine the MECHATROLINK cable connection.
EF0YaskawaGA800Option Card External FaultFaultThe communication option received an external fault from the controller.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input from the controller.
EF1YaskawaGA800External Fault (Terminal S1)FaultMFDI terminal S1 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF2YaskawaGA800External Fault (Terminal S2)FaultMFDI terminal S2 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF3YaskawaGA800External Fault (Terminal S3)FaultMFDI terminal S3 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF4YaskawaGA800External Fault (Terminal S4)FaultMFDI terminal S4 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF5YaskawaGA800External Fault (Terminal S5)FaultMFDI terminal S5 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF6YaskawaGA800External Fault (Terminal S6)FaultMFDI terminal S6 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF7YaskawaGA800External Fault (Terminal S7)FaultMFDI terminal S7 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
EF8YaskawaGA800External Fault (Terminal S8)FaultMFDI terminal S8 caused an external fault through an external device.1. Find the device that caused the external fault and remove the cause. 2. Clear the external fault input in the MFDI.
ErrYaskawaGA800EEPROM Write ErrorFaultThere was a problem with the EEPROM hardware.• Re-energize the drive. • If the fault stays, replace the control board or the drive. Contact Yaskawa or your nearest sales representative to replace the board.
FAnYaskawaGA800Internal Fan FaultFaultThe circulation fan stopped operating correctly.• Examine circulation fan operation. • Re-energize the drive. • Examine U4-03 [Cooling Fan Ope Time] and U4-04 [Cool Fan Maintenance]. If there is damage to the circulation fan or if the performance life of the fan is expired, replace the fan.
FAn1YaskawaGA800Drive Cooling Fan FaultFaultThe cooling fan stopped operating correctly.• Examine cooling fan operation. • Re-energize the drive. • Examine U4-03 [Cooling Fan Ope Time] and U4-04 [Cool Fan Maintenance]. If the performance life of the cooling fan is expired or if there is damage to the fan, replace the fan.
FbHYaskawaGA800Excessive PID FeedbackFaultThe FbH detection level is set incorrectly.Adjust b5-36 [PID High Feedback Detection Lvl] and b5-37 [PID High Feedback Detection Time].
FbLYaskawaGA800PID Feedback LossFaultThe FbL detection level is set incorrectly.Adjust b5-13 [PID Feedback Loss Detection Lvl] and b5-14 [PID Feedback Loss Detection Time].
GFYaskawaGA800Ground FaultFaultOverheating caused damage to the motor or the motor insulation is not satisfactory.Measure the motor insulation resistance, and replace the motor if there is electrical conduction or unserviceable insulation.
HLCEYaskawaGA800High Level Communication ErrorsFault
LFYaskawaGA800Output Phase LossFaultThe motor main circuit cable is disconnected.Connect motor main circuit cable wiring.
LF2YaskawaGA800Output Current ImbalanceFaultThere is phase loss in the wiring on the output side of the drive.Examine for wiring errors or disconnected wires on the output side of the drive, and repair problems.
LSoYaskawaGA800Low Speed Motor Step-OutFaultThe motor code set incorrectly.• Set E5-01 [PM Motor Code Selection] correctly as specified by the motor. • For specialized motors, refer to the motor test report and set E5- xx correctly.
nSEYaskawaGA800Node Setup ErrorFault
oCYaskawaGA800OvercurrentFaultThe load is too heavy.• Measure the current flowing into the motor. • Replace the drive with a larger capacity model if the current value is more than the drive rated current. • Decrease the load or replace with a larger drive to prevent sudden changes in the current level.
oFA00YaskawaGA800Option Not Compatible with PortFaultThe option connected to connector CN5-A is not compatible.Connect the option to the correct connector.
oFA01YaskawaGA800Option Fault/Connection ErrorFault
oFA02YaskawaGA800Duplicate OptionsFaultThe same option cards or the same type of option cards are connected to connectors CN5-A, B, and C.Connect the option card to the correct connector.
oFb00YaskawaGA800Option Not Compatible with PortFaultThe option connected to connector CN5-B is not compatible.Connect the option to the correct connector.
oFb01YaskawaGA800Option Fault/Connection ErrorFault
oFb02YaskawaGA800Duplicate OptionsFaultThe same option cards or the same type of option cards are connected to connectors CN5-A, B, and C.Connect the option card to the correct connector.
oFC00YaskawaGA800Option Not Compatible with PortFaultThe option connected to connector CN5-C is not compatible.Connect the option to the correct connector.
oFC01YaskawaGA800Option Fault/Connection ErrorFault
oFC02YaskawaGA800Duplicate OptionsFaultThe same option cards or the same type of option cards are connected to connectors CN5-A, B, and C.Connect the option card to the correct connector.
oHYaskawaGA800Heatsink OverheatFaultThe ambient temperature is high and the heatsink temperature of the drive is more than the value set in L8-02 [Overheat Alarm Level].• Measure the ambient temperature. • Increase the airflow in the control panel. • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature. • Remove objects near the drive that are producing too much heat.
oH1YaskawaGA800Heatsink OverheatFaultThe ambient temperature is high and the heatsink temperature of the drive is more than the oH1 detection level.• Measure the ambient temperature. • Increase the airflow in the control panel. • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature. • Remove objects near the drive that are producing too much heat.
oH3YaskawaGA800Motor Overheat (PTC Input)FaultThe thermistor wiring that detects motor temperature is defective.Correct wiring errors.
oH4YaskawaGA800Motor Overheat Fault (PTC Input)FaultThe motor has overheated.• Check the load level, acceleration/deceleration time, and motor start/stop frequency (cycle time). • Decrease the load. • Increase the values set in C1-01 to C1-08 [Acceleration/ Deceleration Times]. • Set E2-01 [Motor Rated Current (FLA)] correctly to the value specified by the motor nameplate. • Make sure that the motor cooling system is operating correctly, and repair or replace it if it is damaged. • Adjust E1-04 to E1-10 [V/f Pattern Parameters]. For motor 2, adjust E3-04 to E3-10. Decrease the values set in E1-08 [Mid Point A Voltage] and E1-10 [Minimum Output Voltage].
oL1YaskawaGA800Motor OverloadFaultThe load is too heavy.Decrease the load.
oL2YaskawaGA800Drive OverloadFaultThe load is too large.Decrease the load.
oL3YaskawaGA800Overtorque Detection 1Fault
oL4YaskawaGA800Overtorque Detection 2Fault
oL5YaskawaGA800Mechanical Weakening Detection 1FaultThe drive detected overtorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select].Do a deterioration diagnostic test on the machine side.
oL7YaskawaGA800High Slip Braking OverloadFault
oPrYaskawaGA800Keypad Connection FaultFaultThe keypad is not securely connected to the connector on the drive.Examine the connection between the keypad and the drive.
oSYaskawaGA800OverspeedFaultThere is overshoot.• Decrease C5-01 [ASR Proportional Gain 1] and increase C5-02 [ASR Integral Time 1]. • Adjust the pulse train gain with H6-02 to H6-05 [Pulse Train Input Setting Parameters].
ovYaskawaGA800OvervoltageFaultThe deceleration time is too short and too much regenerative energy is flowing back into the drive.1. Set L3-04 = 1 [Stall Prevention during Decel = General Purpose]. 2. Increase the values set in C1-02, C1-04, C1-06, or C1-08 [Deceleration Times]. 3. Connect a dynamic braking option to the drive. 4. Perform Deceleration Rate Tuning.
PE1YaskawaGA800PLC Fault 1Fault
PE2YaskawaGA800PLC Fault 2Fault
PFYaskawaGA800Input Phase LossFaultThere is a phase loss in the drive input power.Correct errors with the wiring for main circuit drive input power.
PGoYaskawaGA800Encoder (PG) Feedback LossFaultThe encoder cable is disconnected or wired incorrectly.Examine for wiring errors or disconnected wires in the encoder cable, and repair problems.
PGoHYaskawaGA800Encoder (PG) Hardware FaultFaultThe encoder cable is disconnected.Correct any disconnected wires in the encoder cable.
PSEYaskawaGA800JOHB-SMP3 Protocol Set ErrorFault
rFYaskawaGA800Braking Resistor FaultFaultThe resistance of the dynamic braking option that is connected to the drive is too low.Use a dynamic braking option that fits the model and duty rating of the drive.
rHYaskawaGA800Braking Resistor OverheatFaultThe deceleration time is too short and excessive regenerative energy is flowing back into the drive.• Check the load level, deceleration time, and speed. • Decrease the load. • Increase the values set in C1-02, C1-04, C1-06, or C1-08 [Deceleration Times]. • Use a dynamic braking option that lets you use more power.
SCYaskawaGA800Short Circuit/ IGBT FailureFaultOverheating caused damage to the motor or the motor insulation is not satisfactory.Measure the motor insulation resistance, and replace the motor if there is electrical conduction or unserviceable insulation.
SCFYaskawaGA800Safety Circuit FaultFaultThe safety circuit is broken.Replace the control board or the drive.
SErYaskawaGA800Speed Search Retries ExceededFaultThe speed search-related parameters are set incorrectly.• Decrease b3-10 [Speed Estimation Detection Gain]. • Increase b3-17 [Speed Est Retry Current Level]. • Increase b3-18 [Speed Est Retry Detection Time]. • Do Auto-Tuning again.
STPoYaskawaGA800Motor Step-Out DetectedFaultThe motor code is set incorrectly for PM Control Methods.• Set E5-01 [PM Motor Code Selection] correctly as specified by the motor. • For specialized motors, refer to the motor test report and set E5- xx correctly.
SvEYaskawaGA800Zero Servo FaultFaultThe value set in the torque limit is too small.Adjust torque limit-related parameters L7-01 to L7-04.
TiMYaskawaGA800Keypad Time Not SetFaultThere is a battery in the keypad, but the date and time are not set.Use the keypad to set the date and time.
UL3YaskawaGA800Undertorque Detection 1Fault
UL4YaskawaGA800Undertorque Detection 2Fault
UL5YaskawaGA800Mechanical Weakening Detection 2FaultThe drive detected undertorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select].Examine the machine for deterioration.
Uv1YaskawaGA800DC Bus UndervoltageFaultThere is a phase loss in the drive input power.Correct errors with the wiring for main circuit drive input power.
Uv2YaskawaGA800Control Power UndervoltageFaultThe value set in L2-02 [Power Loss Ride Through Time] increased and the momentary power loss recovery unit is not connected to the drive.Connect the momentary power loss recovery unit to the drive.
Uv3YaskawaGA800Soft Charge Answerback FaultFault
bUSyYaskawaGA800BusyNot an alarm.You set the drive to use MEMOBUS/Modbus communications to change parameters, but you used the keypad to change parameters.Use MEMOBUS/Modbus communications to enter the enter command, then use the keypad to change the parameter.
CrSTYaskawaGA800Remove RUN Command to ResetNot an alarm.
ovErYaskawaGA800Too Many Parameters ChangedNot an alarm.You tried to change more than 150 parameters.Make sure that parameters that do not have an effect on drive operation are at their default settings.
PASSYaskawaGA800Modbus Communication TestNot an alarm.
oPE01YaskawaGA800Drive Capacity Setting FaultParameter Setting Error
oPE02YaskawaGA800Parameter Range Setting ErrorParameter Setting Error
oPE03YaskawaGA800Multi-Function Input Setting ErrParameter Setting Error
oPE05YaskawaGA800Run Cmd/Freq Ref Source Sel ErrParameter Setting ErrorThe setting to assign the Run command or frequency reference to an option card or the pulse train input is incorrect.Correct the parameter settings.
oPE06YaskawaGA800Control Method Selection ErrorParameter Setting ErrorA1-02 = 1, 3, or 7 [Control Method Selection = CL- V/f, CLV, CLV/PM], but there is no encoder option connected the drive.• Connect an encoder option the drive. • Set A1-02 correctly.
oPE07YaskawaGA800Analog Input Selection ErrorParameter Setting ErrorThe settings for H3-02, H3-06, and H3-10 [MFAI Function Select] and H7-30 [Virtual Analog Input Selection] overlap.Set H3-02, H3-06, H3-10, and H7-30 correctly to prevent overlap.
oPE08YaskawaGA800Parameter Selection ErrorParameter Setting Error
oPE09YaskawaGA800PID Control Selection FaultParameter Setting ErrorThese parameters are set at the same time: • b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz] • b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer] • Set b5-15 ≠ 0.0.• Set b1-03 = 0, 1 [Ramp to Stop, Coast to Stop].
oPE10YaskawaGA800V/f Data Setting ErrorParameter Setting Error
oPE11YaskawaGA800Carrier Frequency Setting ErrorParameter Setting Error
oPE13YaskawaGA800Pulse Monitor Selection ErrorParameter Setting ErrorH6-06 = 101, 102, 105, or 116 [Terminal MP Monitor Selection = Frequency Reference, Output Frequency, Motor Speed, Output Frequency after Soft Starter] has not been set when H6-07 = 0 [Terminal MP Frequency Scaling = 0 Hz].Set H6-06 correctly.
oPE15YaskawaGA800Torque Control Setting ErrorParameter Setting Error
oPE16YaskawaGA800Energy Saving Constants ErrorParameter Setting ErrorThe Energy Saving parameters are not set in the applicable setting range.Make sure that E5-xx is set correctly as specified by the motor nameplate data.
oPE18YaskawaGA800Online Tuning Param Setting ErrParameter Setting Error
oPE20YaskawaGA800PG-F3 Setting ErrorParameter Setting ErrorThe value set in F1-01 [Encoder 1 Pulse Count (PPR)] does not agree with the number of encoder pulses.• Examine the F1-01 value and the number of encoder pulses. • Set F1-01 correctly.
oPE33YaskawaGA800Digital Output Selection ErrorParameter Setting Error
F2Allen-BradleyPowerFlex 40Auxiliary InputAuxiliary input interlock is open.1. Check remote wiring. 2. Verify communications programming for intentional fault.
F3Allen-BradleyPowerFlex 40Power LossExcessive DC Bus voltage ripple.1. Monitor the incoming line for phase loss or line imbalance. 2. Check input line fuse.
F4Allen-BradleyPowerFlex 40UnderVoltageDC bus voltage fell below the minimum value.Monitor the incoming AC line for low voltage or line power interruption.
F5Allen-BradleyPowerFlex 40OverVoltageDC bus voltage exceeded maximum value.Monitor the AC line for high line voltage or transient conditions. Bus overvoltage can also be caused by motor regeneration. Extend the decel time or install dynamic brake option.
F6Allen-BradleyPowerFlex 40Motor StalledDrive is unable to accelerate motor.Increase P039…A067 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit 1].
F7Allen-BradleyPowerFlex 40Motor OverloadInternal electronic overload trip.1. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. 2. Verify A084 [Boost Select] setting
F8Allen-BradleyPowerFlex 40Heatsink OvrTmp
F12Allen-BradleyPowerFlex 40HW OverCurrentThe drive output current has exceeded the hardware current limit.Check programming. Check for excess load, improper A084 [Boost Select] setting, DC brake voltssettoo high or other causes of excess current.
F13Allen-BradleyPowerFlex 40Ground FaultA current path to earth ground has been detected at one or more of the drive output terminals.Check the motor and external wiring to the drive output terminals for a grounded condition.
F29Allen-BradleyPowerFlex 40Analog Input Loss
F33Allen-BradleyPowerFlex 40Auto Rstrt TriesDrive unsuccessfully attempted to reset a fault and resume running for the programmed number of A092 [Auto Rstrt Tries].Correct the cause of the fault and manually clear.
F38Allen-BradleyPowerFlex 40Phase U to Gnd
F39Allen-BradleyPowerFlex 40Phase V to Gnd
F40Allen-BradleyPowerFlex 40Phase W to Gnd
F41Allen-BradleyPowerFlex 40Phase UV ShortExcessive current has been detected between these two output terminals.1. Check the motor and drive output terminal wiring for a shorted condition. 2. Replace drive if fault cannot be cleared.
F43Allen-BradleyPowerFlex 40Phase VW ShortExcessive current has been detected between these two output terminals.1. Check the motor and drive output terminal wiring for a shorted condition. 2. Replace drive if fault cannot be cleared.
F48Allen-BradleyPowerFlex 40Params DefaultedThe drive was commanded to write default values to EEPROM.1. Clear the fault or cycle power to the drive. 2. Program the drive parameters as needed.
F63Allen-BradleyPowerFlex 40SW OverCurrentProgrammed A098 [SW Current Trip] has been exceeded.Check load requirements and A098 [SW Current Trip] setting.
F64Allen-BradleyPowerFlex 40Drive OverloadDrive rating of 150% for 1 minute or 200% for 3 seconds has been exceeded.Reduce load or extend Accel Time.
F70Allen-BradleyPowerFlex 40Power UnitFailure hasbeen detected in the drive power section.1. Cycle power. 2. Replace drive if fault cannot be cleared.
F71Allen-BradleyPowerFlex 40Net Loss
F80Allen-BradleyPowerFlex 40SVC Autotune
F81Allen-BradleyPowerFlex 40Comm LossRS-485 (DSI) port stopped communicating.1. If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using A105 [Comm Loss Action].
F100Allen-BradleyPowerFlex 40Parameter ChecksumThe checksum read from the board does not match the checksum calculated.Set P041 [Reset To Defalts] to option 1 “Reset Defaults”.
F122Allen-BradleyPowerFlex 40I/O Board FailFailure hasbeen detected in the drive control and I/O section.1. Cycle power. 2. Replace drive if fault cannot be cleared.
2DanfossFC 301/302Live zero errorWARNING/ALARMThis warning or alarm only appears if programmed in parameter 6-01 Live Zero Timeout Function. The signal on 1 of the analog inputs is less than 50% of the minimum value programmed for that input. Broken wiring or a faulty device sending the signal can cause this condition.• Check connections on all analog mains terminals. - Control card terminals 53 and 54 for signals, terminal 55 common. - VLT® General Purpose I/O MCB 101 terminals 11 and 12 for signals, terminal 10 common. - VLT® Analog I/O Option MCB 109 terminals 1, 3, and 5 for signals, terminals 2, 4, and 6 common. • Check that the drive programming and switch settings match the analog signal type. • Perform an input terminal signal test.
3DanfossFC 301/302No motorWARNING/ALARMNo motor is connected to the output of the frequency converter.
4DanfossFC 301/302Mains phase lossWARNING/ALARMA phase is missing on the supply side, or the mains voltage imbalance is too high. This message also appears for a fault in the input rectifier. Options are programmed in parameter 14-12 Response to Mains Imbalance.• Check the supply voltage and supply currents to the frequency converter.
7DanfossFC 301/302DC overvoltageWARNING/ALARM
8DanfossFC 301/302DC under voltageWARNING/ALARMIf the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size.• Check that the supply voltage matches the drive voltage. • Perform an input voltage test. • Perform a soft-charge circuit test.
9DanfossFC 301/302Inverter overloadWARNING/ALARMThe frequency converter has run with more than 100% overload for too long and is about to cut out. The counter for electronic thermal inverter protection issues a warning at 98% and trips at 100% with an alarm. The frequency converter cannot be reset until the counter is below 90%.• Compare the output current shown on the LCP with the frequency converter rated current. • Compare the output current shown on the LCP with the measured motor current. • Show the thermal frequency converter load on the LCP and monitor the value. When running above the frequency converter continuous current rating, the counter increases. When running below the frequency converter continuous current rating, the counter decreases.
10DanfossFC 301/302Motor overload temperatureWARNING/ALARMAccording to the electronic thermal protection (ETR), the motor is too hot. Select 1 of these options: • The frequency converter issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options. • The frequency converter trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options. The fault occurs when the motor runs with more than 100% overload for too long.• Check for motor overheating. • Check if the motor is mechanically overloaded. • Check that the motor current set in parameter 1-24 Motor Current is correct. • Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. • If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan. • Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.
11DanfossFC 301/302Motor thermistor overtempWARNING/ALARMCheck whether the thermistor is disconnected. Select whether the frequency converter issues a warning or an alarm in parameter 1-90 Motor Thermal Protection.• Check for motor overheating. • Check if the motor is mechanically overloaded. • When using terminal 53 or 54, check that the thermistor is connected correctly between either terminal 53 or 54 (analog voltage input) and terminal 50 (+10 V supply). Also check that the terminal switch for 53 or 54 is set for voltage. Check that parameter 1-93 Thermistor Resource selects terminal 53 or 54. • When using terminal 18, 19, 31, 32, or 33 (digital inputs), check that the thermistor is connected correctly between the digital input terminal used (digital input PNP only) and terminal 50. Select the terminal to use in parameter 1-93 Thermistor Resource.
12DanfossFC 301/302Torque limitWARNING/ALARMThe torque has exceeded the value in parameter 4-16 Torque Limit Motor Mode or the value in parameter 4-17 Torque Limit Generator Mode. Parameter 14-25 Trip Delay at Torque Limit can change this warning from a warning-only condition to a warning followed by an alarm.• If the motor torque limit is exceeded during ramp-up, extend the ramp-up time. • If the generator torque limit is exceeded during ramp-down, extend the ramp-down time. • If torque limit occurs while running, increase the torque limit. Make sure that the system can operate safely at a higher torque. • Check the application for excessive current draw on the motor.
13DanfossFC 301/302Over currentWARNING/ALARMThe inverter peak current limit (approximately 200% of the rated current) is exceeded. The warning lasts approximately 1.5 s, then the frequency converter trips and issues an alarm. Shock loading or quick acceleration with high-inertia loads can cause this fault. If the acceleration during ramp- up is quick, the fault can also appear after kinetic back-up. If extended mechanical brake control is selected, a trip can be reset externally.• Remove the power and check if the motor shaft can be turned. • Check that the motor size matches the frequency converter. • Check that the motor data is correct in parameters 1-20 to 1-25.
17DanfossFC 301/302Control word timeoutWARNING/ALARMThere is no communication to the frequency converter. The warning is only active when parameter 8-04 Control Word Timeout Function is NOT set to [0] Off. If parameter 8-04 Control Word Timeout Function is set to [5] Stop and trip, a warning appears, and the frequency converter ramps down to a stop and shows an alarm.• Check the connections on the serial communi- cation cable. • Increase parameter 8-03 Control Word Timeout Time. • Check the operation of the communication equipment. • Verify that proper EMC installation was performed.
20DanfossFC 301/302Temp. input errorWARNING/ALARMThe temperature sensor is not connected.
21DanfossFC 301/302Parameter errorWARNING/ALARMThe parameter is out of range. The parameter number is shown in the display.• Set the affected parameter to a valid value.
22DanfossFC 301/302Hoist mechanical brakeWARNING/ALARMThe value of this warning/alarm shows the type of warning/alarm. 0 = The torque reference was not reached before timeout (parameter 2-27 Torque Ramp Time). 1 = Expected brake feedback was not received before timeout (parameter 2-23 Activate Brake Delay, parameter 2-25 Brake Release Time).
26DanfossFC 301/302Brake resistor power limitWARNING/ALARMThe power transmitted to the brake resistor is calculated as a mean value over the last 120 s of run time. The calculation is based on the DC-link voltage and the brake resistor value set in parameter 2-16 AC brake Max. Current. The warning is active when the dissipated braking power is higher than 90% of the brake resistor power. If option [2] Trip is selected in parameter 2-13 Brake Power Monitoring, the frequency converter trips when the dissipated braking power reaches 100%.
27DanfossFC 301/302Brake chopper faultWARNING/ALARMThe brake transistor is monitored during operation, and if a short circuit occurs, the brake function is disabled, and a warning is issued. The frequency converter is still operational, but since the brake transistor has short- circuited, substantial power is transmitted to the brake resistor, even if it is inactive.• Remove power to the frequency converter and remove the brake resistor.
28DanfossFC 301/302Brake check failedWARNING/ALARMThe brake resistor is not connected or not working.• Check parameter 2-15 Brake Check.
34DanfossFC 301/302Fieldbus communication faultWARNING/ALARMThe fieldbus on the communication option card is not working.
35DanfossFC 301/302Option faultWARNING/ALARMAn option alarm is received. The alarm is option-specific. The most likely cause is a power-up or a communication fault.
36DanfossFC 301/302Mains failureWARNING/ALARMThis warning/alarm is only active if the supply voltage to the frequency converter is lost and parameter 14-10 Mains Failure is not set to [0] No function.• Check the fuses to the frequency converter and mains supply to the unit.
61DanfossFC 301/302Feedback errorWARNING/ALARMAn error between calculated speed and speed measurement from feedback device.• Check the settings for warning/alarm/disabling in parameter 4-30 Motor Feedback Loss Function. • Set the tolerable error in parameter 4-31 Motor Feedback Speed Error. • Set the tolerable feedback loss time in parameter 4-32 Motor Feedback Loss Timeout.
62DanfossFC 301/302Output frequency at maximumWARNING/ALARMlimit If the output frequency reaches the value set in parameter 4-19 Max Output Frequency, the frequency converter issues a warning. The warning ceases when the output drops below the maximum limit. If the frequency converter is unable to limit the frequency, it trips and issues an alarm. The latter may happen in the flux mode if the frequency converter loses control of the motor.• Check the application for possible causes. • Increase the output frequency limit. Ensure that the system can operate safely at a higher output frequency.
65DanfossFC 301/302Control card over temperatureWARNING/ALARMThe cutout temperature of the control card is 85 °C (185 °F).• Check that the ambient operating temperature is within the limits. • Check for clogged filters. • Check the fan operation. • Check the control card.
101DanfossFC 301/302Speed monitorWARNING/ALARMThe motor speed monitor value is out of range. See parameter 4-43 Motor Speed Monitor Function.
104DanfossFC 301/302Mixing fan faultWARNING/ALARMThe fan is not operating. The fan monitor checks that the fan is spinning at power-up or whenever the mixing fan is turned on. The mixing-fan fault can be configured as a warning or an alarm trip in parameter 14-53 Fan Monitor.• Cycle power to the frequency converter to determine if the warning/alarm returns.
122DanfossFC 301/302Mot. rotat. unexp.WARNING/ALARMThe frequency converter performs a function that requires the motor to be at standstill, for example DC hold for PM motors.
157DanfossFC 301/302Power Limit Mot.WARNING/ALARMThe output power exceeds the value defined in parameter 4-82 Power Limit Motor Mode.
158DanfossFC 301/302Power Limit Gen.WARNING/ALARMThe generating power exceeds the value defined in parameter 4-83 Power Limit Generator Mode.
210DanfossFC 301/302Position trackingWARNING/ALARMThe actual position error exceeds the value in parameter 4-71 Maximum Position Error. Parameter 4-70 Position Error Function defines whether this is a warning or an alarm.
211DanfossFC 301/302Position limitWARNING/ALARMThe position is outside the limits defined in parameter 3-06 Minimum Position and parameter 3-07 Maximum Position. Parameter 4-73 Position Limit Function defines the function for this warning/alarm.
212DanfossFC 301/302Homing not doneWARNING/ALARMA homing function is selected in parameter 17-80 Homing Function and absolute positioning is executed before homing is completed.
215DanfossFC 301/302Start Fwd/RevWARNING/ALARMOne of the hardware end-limit options, [12] Enable Start Forward or [13] Enable Start Reverse is active.
216DanfossFC 301/302Touch TimeoutWARNING/ALARMA touch probe sensor is not found within the time in parameter 4-75 Touch Timout. The timeout timer is started as soon as the touch probe positioning is activated even if the application is not moving.
1DanfossFC 301/30210 Volts lowWARNINGThe control card voltage is less than 10 V from terminal 50. Remove some of the load from terminal 50, as the 10 V supply is overloaded. Maximum 15 mA or minimum 590 Ω. A short circuit in a connected potentiometer or incorrect wiring of the potentiometer can cause this condition.• Remove the wiring from terminal 50. If the warning clears, the problem is with the wiring. If the warning does not clear, replace the control card.
5DanfossFC 301/302DC link voltage highWARNINGThe DC-link voltage (DC) is higher than the high-voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
6DanfossFC 301/302DC link voltage lowWARNINGThe DC-link voltage (DC) is lower than the low voltage warning limit. The limit depends on the drive voltage rating. The unit is still active.
23DanfossFC 301/302Internal fan faultWARNINGThe fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled). For frequency converters with DC fans, a feedback sensor is mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. For frequency converters with AC fans, the voltage to the fan is monitored.• Check for proper fan operation. • Cycle power to the frequency converter and check that the fan operates briefly at start-up. • Check the sensors on the control card.
24DanfossFC 301/302External fan faultWARNINGThe fan warning function is a protective function that checks if the fan is running/mounted. The fan warning can be disabled in parameter 14-53 Fan Monitor ([0] Disabled). For frequency converters with DC fans, a feedback sensor is mounted in the fan. If the fan is commanded to run and there is no feedback from the sensor, this alarm appears. For frequency converters with AC fans, the voltage to the fan is monitored.• Check for proper fan operation. • Cycle power to the frequency converter and check that the fan operates briefly at start-up. • Check the sensors on the heat sink.
25DanfossFC 301/302Brake resistor short circuitWARNINGThe brake resistor is monitored during operation. If a short circuit occurs, the brake function is disabled and the warning appears. The frequency converter is still operational, but without the brake function.• Remove the power to the frequency converter and replace the brake resistor (refer to parameter 2-15 Brake Check).
40DanfossFC 301/302Overload of digital output terminal 27WARNINGCheck the load connected to terminal 27 or remove the short-circuit connection. Check parameter 5-00 Digital I/O Mode and parameter 5-01 Terminal 27 Mode.
41DanfossFC 301/302Overload of digital output terminal 29WARNINGCheck the load connected to terminal 29 or remove the short-circuit connection. Also check parameter 5-00 Digital I/O Mode and parameter 5-02 Terminal 29 Mode.
47DanfossFC 301/30224 V supply lowWARNINGThe supply on the power card is out of range. There are 3 supplies generated by the switch mode supply (SMPS) on the power card: • 24 V. • 5 V. • ±18 V.• Check for a defective power card.
48DanfossFC 301/3021.8 V supply lowWARNINGThe 1.8 V DC supply used on the control card is outside of the allowable limits. The supply is measured on the control card.• Check for a defective control card. • If an option card is present, check for overvoltage.
49DanfossFC 301/302Speed limitWARNINGThe warning is shown when the speed is outside of the specified range in parameter 4-11 Motor Speed Low Limit [RPM] and parameter 4-13 Motor Speed High Limit [RPM].
59DanfossFC 301/302Current limitWARNINGThe current is higher than the value in parameter 4-18 Current Limit. Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit.
60DanfossFC 301/302External interlockWARNINGA digital input signal indicates a fault condition external to the frequency converter. An external interlock has commanded the frequency converter to trip. Clear the external fault condition. To resume normal operation, apply 24 V DC to the terminal programmed for external interlock, and reset the frequency converter.
64DanfossFC 301/302Voltage limitWARNINGThe combination of load and speed requires a motor voltage higher than the actual DC-link voltage.
66DanfossFC 301/302Heat sink temperature lowWARNING
73DanfossFC 301/302Safe Stop auto restartWARNINGSTO activated. With automatic restart enabled, the motor can start when the fault is cleared.
76DanfossFC 301/302Power unit setupWARNINGThe required number of power units do not match the detected number of active power units. This warning occurs when replacing a module for an F-size enclosure if the power-specific data in the module power card does not match the rest of the frequency converter.• Confirm that the spare part and its power card are the correct part number.
77DanfossFC 301/302Reduced power modeWARNINGThe frequency converter is operating in reduced power mode (less than the allowed number of inverter sections). This warning is generated on power cycle when the frequency converter is set to run with fewer inverters and remains on.
89DanfossFC 301/302Mechanical brake slidingWARNINGThe hoist brake monitor detects a motor speed exceeding 10 RPM.
123DanfossFC 301/302Motor Mod. ChangedWARNINGThe motor selected in parameter 1-11 Motor Model is not correct. Check the motor model.
163DanfossFC 301/302ATEX ETR cur.lim.warningWARNINGThe frequency converter has run above the characteristic curve for more than 50 s. The warning is activated at 83% and deactivated at 65% of the allowed thermal overload.
165DanfossFC 301/302ATEX ETR freq.lim.warningWARNINGThe frequency converter is running for more than 50 s below the allowed minimum frequency (parameter 1-98 ATEX ETR interpol. points freq.).
220DanfossFC 301/302Configuration file version not supportedWARNINGThe frequency converter does not support the current configuration file version. Customization is aborted.
249DanfossFC 301/302Rect. low temperatureWARNINGThe temperature of the rectifier heat sink is lower than expected.• Check the temperature sensor.
250DanfossFC 301/302New spare partWARNINGThe power or switch mode supply has been exchanged. Restore the frequency converter type code in the EEPROM. Select the correct type code in parameter 14-23 Typecode Setting according to the label on the frequency converter. Remember to select Save to EEPROM at the end.
251DanfossFC 301/302New typecodeWARNINGThe power card or other components are replaced, and the type code has changed.
253DanfossFC 301/302Digital output X49/9 overloadWARNINGDigital output X49/9 is overloaded.
254DanfossFC 301/302Digital output X49/11 overloadWARNINGDigital output X49/11 is overloaded.
255DanfossFC 301/302Digital output X49/7 overloadWARNINGDigital output X49/7 is overloaded.

Where this came from

Every record above links the page it was taken from and quotes the sentence that states it. These are the 3 sources this dataset was assembled from.

Machine-readable

From your own code

Same records, same quotes, without scraping the page: refsource is on PyPI and npm. Each value comes back carrying the URL it was read from and the sentence on that page that states it — .source and .quote sit on the value itself rather than in a side channel, so the checking step is available instead of skipped.

pip install refsource
refsource lookup industrial-vfd-fault-alarm-codes-by-brand brand=Danfoss

npx -y refsource lookup industrial-vfd-fault-alarm-codes-by-brand brand=Danfoss

Set your AI assistant up to use this

Two files and no account. Put this in .mcp.json at the root of your project — Claude Code, Cursor, Windsurf, VS Code and Codex all read that file — and your assistant can look this dataset up instead of recalling it. The server is remote, keyless and read-only.

{
  "mcpServers": {
    "referencesource": {
      "type": "http",
      "url": "https://referencesource.org/mcp"
    }
  }
}

Add to Cursor · or, on the command line: claude mcp add --transport http referencesource https://referencesource.org/mcp --scope project

Then one line in the project's CLAUDE.md or AGENTS.md, so the assistant knows when to reach for it:

When a question needs "Industrial VFD fault and alarm codes by brand", call the referencesource MCP server at https://referencesource.org/mcp (tool `search_records`, dataset_slug `industrial-vfd-fault-alarm-codes-by-brand`) instead of answering from memory — every record it returns carries its source URL and a verbatim quote from that page.

What each tool does, and the servers built over single registers: Connect your AI assistant.

340 records. last verified against source . due for re-check by .

Licence. factual compilation from manufacturer technical manuals