F41 · PowerFlex 40

For F41 · PowerFlex 40, brand is Allen-Bradley; model / series is PowerFlex 40; fault code is F41; fault name is Phase UV Short; cause is Excessive current has been detected between these two output terminals, verified against its source on 2026-09-01.

Brand
Allen-Bradley
Model / series
PowerFlex 40
Fault code
F41 verified
Fault name
Phase UV Short verified
Cause
Excessive current has been detected between these two output terminals. verified
Corrective action
1. Check the motor and drive output terminal wiring for a shorted condition. 2. Replace drive if fault cannot be cleared. verified