Reference Source

8 · FC 301/302 · WARNING/ALARM

For 8 · FC 301/302 · WARNING/ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 8; fault name is DC under voltage; type is WARNING/ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
8 verified
Fault name
DC under voltage verified
Type
WARNING/ALARM verified
Cause
If the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size. verified
Corrective action
• Check that the supply voltage matches the drive voltage. • Perform an input voltage test. • Perform a soft-charge circuit test. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

WARNING/ALARM 8, DC under voltage

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

If the DC-link voltage drops below the undervoltage limit, the drive checks for 24 V DC back-up supply. If no 24 V DC back-up supply is connected, the drive trips after a fixed time delay. The time delay varies with unit size.

Corrective action

• Check that the supply voltage matches the drive voltage. • Perform an input voltage test. • Perform a soft-charge circuit test.

— all from files.danfoss.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.