For 14 · FC 301/302 · ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 14; fault name is Earth (ground) fault; type is ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
14 verified
Fault name
Earth (ground) fault verified
Type
ALARM verified
Cause
There is current from the output phase-to-ground, either in the cable between the frequency converter and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the frequency converter and current going into the frequency converter from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the frequency converter must be the same as the current going into the frequency converter. verified
Corrective action
• Remove power to the frequency converter and repair the ground fault. • Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. • Reset any potential individual offset in the 3 current transducers in the frequency converter. Perform the manual initialization or perform a complete AMA. This method is most relevant after changing the power card. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

ALARM 14, Earth (ground) fault

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

There is current from the output phase-to-ground, either in the cable between the frequency converter and the motor, or in the motor itself. The current transducers detect the ground fault by measuring current going out from the frequency converter and current going into the frequency converter from the motor. Ground fault is issued if the deviation of the 2 currents is too large. The current going out of the frequency converter must be the same as the current going into the frequency converter.

Corrective action

• Remove power to the frequency converter and repair the ground fault. • Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. • Reset any potential individual offset in the 3 current transducers in the frequency converter. Perform the manual initialization or perform a complete AMA. This method is most relevant after changing the power card.

— all from files.danfoss.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.