Uv · GA800 · Alarm

For Uv · GA800 · Alarm, brand is Yaskawa; model / series is GA800; fault code is Uv; fault name is Undervoltage; type is Alarm, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
Uv verified
Fault name
Undervoltage verified
Type
Alarm verified
Cause
The drive input power voltage is changing too much. verified
Corrective action
• Examine the input power for problems. • Make the drive input power stable. • If the input power supply is good, examine the magnetic contactor on the main circuit side for problems. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

Uv (0001) Undervoltage Flashing Alarm 134

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The drive input power voltage is changing too much.

Corrective action

• Examine the input power for problems. • Make the drive input power stable. • If the input power supply is good, examine the magnetic contactor on the main circuit side for problems.

— all from yaskawa.com, retrieved 2026-09-01