oPE13 · GA800 · Parameter Setting Error
For oPE13 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE13; fault name is Pulse Monitor Selection Error; type is Parameter Setting Error, verified against its source on 2026-09-01.
- Brand
- Yaskawa
- Model / series
- GA800
- Fault code
- oPE13 verified
- Fault name
- Pulse Monitor Selection Error verified
- Type
- Parameter Setting Error verified
- Cause
- H6-06 = 101, 102, 105, or 116 [Terminal MP Monitor Selection = Frequency Reference, Output Frequency, Motor Speed, Output Frequency after Soft Starter] has not been set when H6-07 = 0 [Terminal MP Frequency Scaling = 0 Hz]. verified
- Corrective action
- Set H6-06 correctly. verified
What the source says
oPE13 Pulse Monitor Selection Error Flashing Parameter Setting Error 139
— yaskawa.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
H6-06 = 101, 102, 105, or 116 [Terminal MP Monitor Selection = Frequency Reference, Output Frequency, Motor Speed, Output Frequency after Soft Starter] has not been set when H6-07 = 0 [Terminal MP Frequency Scaling = 0 Hz].
Corrective action
Set H6-06 correctly.
— all from yaskawa.com, retrieved 2026-09-01