Reference Source

SE · GA800 · Alarm

For SE · GA800 · Alarm, brand is Yaskawa; model / series is GA800; fault code is SE; fault name is Modbus Test Mode Error; type is Alarm, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
SE verified
Fault name
Modbus Test Mode Error verified
Type
Alarm verified
Cause
MEMOBUS/Modbus communications self- diagnostics [H1-xx = 67] was done while the drive was running. verified
Corrective action
Stop the drive and do MEMOBUS/Modbus communications self- diagnostics. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

SE (0020) Modbus Test Mode Error Flashing Alarm 133

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

MEMOBUS/Modbus communications self- diagnostics [H1-xx = 67] was done while the drive was running.

Corrective action

Stop the drive and do MEMOBUS/Modbus communications self- diagnostics.

— all from yaskawa.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.