oPE20 · GA800 · Parameter Setting Error
For oPE20 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE20; fault name is PG-F3 Setting Error; type is Parameter Setting Error, verified against its source on 2026-09-01.
- Brand
- Yaskawa
- Model / series
- GA800
- Fault code
- oPE20 verified
- Fault name
- PG-F3 Setting Error verified
- Type
- Parameter Setting Error verified
- Cause
- The value set in F1-01 [Encoder 1 Pulse Count (PPR)] does not agree with the number of encoder pulses. verified
- Corrective action
- • Examine the F1-01 value and the number of encoder pulses. • Set F1-01 correctly. verified
What the source says
oPE20 PG-F3 Setting Error Flashing Parameter Setting Error 139
— yaskawa.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
The value set in F1-01 [Encoder 1 Pulse Count (PPR)] does not agree with the number of encoder pulses.
Corrective action
• Examine the F1-01 value and the number of encoder pulses. • Set F1-01 correctly.
— all from yaskawa.com, retrieved 2026-09-01
Source
- yaskawa.comhttps://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAIGA8001&cmd=documents&documentName=TOEPYAIGA8001.pdf