STPo · GA800 · Fault

For STPo · GA800 · Fault, brand is Yaskawa; model / series is GA800; fault code is STPo; fault name is Motor Step-Out Detected; type is Fault, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
STPo verified
Fault name
Motor Step-Out Detected verified
Type
Fault verified
Cause
The motor code is set incorrectly for PM Control Methods. verified
Corrective action
• Set E5-01 [PM Motor Code Selection] correctly as specified by the motor. • For specialized motors, refer to the motor test report and set E5- xx correctly. verified