F81 · PowerFlex 40

For F81 · PowerFlex 40, brand is Allen-Bradley; model / series is PowerFlex 40; fault code is F81; fault name is Comm Loss; cause is RS-485 (DSI) port stopped communicating, verified against its source on 2026-09-01.

Brand
Allen-Bradley
Model / series
PowerFlex 40
Fault code
F81 verified
Fault name
Comm Loss verified
Cause
RS-485 (DSI) port stopped communicating. verified
Corrective action
1. If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using A105 [Comm Loss Action]. verified
Sourceliterature.rockwellautomation.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

F81 Comm Loss

literature.rockwellautomation.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

RS-485 (DSI) port stopped communicating.

Corrective action

1. If adapter was not intentionally disconnected, check wiring to the port. Replace wiring, port expander, adapters or complete drive as required. 2. Check connection. 3. An adapter was intentionally disconnected. 4. Turn off using A105 [Comm Loss Action].