F100 · PowerFlex 40
For F100 · PowerFlex 40, brand is Allen-Bradley; model / series is PowerFlex 40; fault code is F100; fault name is Parameter Checksum; cause is The checksum read from the board does not match the checksum calculated, verified against its source on 2026-09-01.
- Brand
- Allen-Bradley
- Model / series
- PowerFlex 40
- Fault code
- F100 verified
- Fault name
- Parameter Checksum verified
- Cause
- The checksum read from the board does not match the checksum calculated. verified
- Corrective action
- Set P041 [Reset To Defalts] to option 1 “Reset Defaults”. verified
Verified
Review by
What the source says
Parameter Checksum, F100, 94
— literature.rockwellautomation.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
The checksum read from the board does not match the checksum calculated.
Corrective action
Set P041 [Reset To Defalts] to option 1 “Reset Defaults”.
— all from literature.rockwellautomation.com, retrieved 2026-09-01
Source
- literature.rockwellautomation.comhttps://literature.rockwellautomation.com/idc/groups/literature/documents/um/22b-um001_-en-e.pdf