10 · FC 301/302 · WARNING/ALARM

For 10 · FC 301/302 · WARNING/ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 10; fault name is Motor overload temperature; type is WARNING/ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
10 verified
Fault name
Motor overload temperature verified
Type
WARNING/ALARM verified
Cause
According to the electronic thermal protection (ETR), the motor is too hot. Select 1 of these options: • The frequency converter issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options. • The frequency converter trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options. The fault occurs when the motor runs with more than 100% overload for too long. verified
Corrective action
• Check for motor overheating. • Check if the motor is mechanically overloaded. • Check that the motor current set in parameter 1-24 Motor Current is correct. • Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. • If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan. • Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

WARNING/ALARM 10, Motor overload temperature

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

According to the electronic thermal protection (ETR), the motor is too hot. Select 1 of these options: • The frequency converter issues a warning or an alarm when the counter is >90% if parameter 1-90 Motor Thermal Protection is set to warning options. • The frequency converter trips when the counter reaches 100% if parameter 1-90 Motor Thermal Protection is set to trip options. The fault occurs when the motor runs with more than 100% overload for too long.

Corrective action

• Check for motor overheating. • Check if the motor is mechanically overloaded. • Check that the motor current set in parameter 1-24 Motor Current is correct. • Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. • If an external fan is in use, check that it is selected in parameter 1-91 Motor External Fan. • Running AMA in parameter 1-29 Automatic Motor Adaptation (AMA) tunes the frequency converter to the motor more accurately and reduces thermal loading.

— all from files.danfoss.com, retrieved 2026-09-01