For 59 · FC 301/302 · WARNING, brand is Danfoss; model / series is FC 301/302; fault code is 59; fault name is Current limit; type is WARNING, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
59 verified
Fault name
Current limit verified
Type
WARNING verified
Cause
The current is higher than the value in parameter 4-18 Current Limit. Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

WARNING 59, Current limit

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

The value above is stated away from the sentence quoted with the answer, so the passage that states it is shown here too.

Cause

The current is higher than the value in parameter 4-18 Current Limit. Ensure that the motor data in parameters 1-20 to 1-25 is set correctly. Increase the current limit if necessary. Ensure that the system can operate safely at a higher limit.