Er-16 · GA800 · Auto-Tuning Error

For Er-16 · GA800 · Auto-Tuning Error, brand is Yaskawa; model / series is GA800; fault code is Er-16; fault name is Inertia ID Error; type is Auto-Tuning Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
Er-16 verified
Fault name
Inertia ID Error verified
Type
Auto-Tuning Error verified
Cause
The inertia found by the drive was too small or too large during Inertia Tuning (10% or less, or 50000% or more). verified
Corrective action
• Decrease the values set for the frequency and amplitude of the test signals used when doing inertia tuning. First, decrease the test signal amplitude, and then do Inertia Tuning. If the error continues, decrease the test signal frequency and do Inertia Tuning again. • Correctly set the motor inertia as specified by the motor, and do Inertia Tuning again. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

Er-16 Inertia ID Error Flashing Auto-Tuning Error 144

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The inertia found by the drive was too small or too large during Inertia Tuning (10% or less, or 50000% or more).

Corrective action

• Decrease the values set for the frequency and amplitude of the test signals used when doing inertia tuning. First, decrease the test signal amplitude, and then do Inertia Tuning. If the error continues, decrease the test signal frequency and do Inertia Tuning again. • Correctly set the motor inertia as specified by the motor, and do Inertia Tuning again.

— all from yaskawa.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.