Reference Source

oPE07 · GA800 · Parameter Setting Error

For oPE07 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE07; fault name is Analog Input Selection Error; type is Parameter Setting Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
oPE07 verified
Fault name
Analog Input Selection Error verified
Type
Parameter Setting Error verified
Cause
The settings for H3-02, H3-06, and H3-10 [MFAI Function Select] and H7-30 [Virtual Analog Input Selection] overlap. verified
Corrective action
Set H3-02, H3-06, H3-10, and H7-30 correctly to prevent overlap. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

oPE07 Analog Input Selection Error Flashing Parameter Setting Error 137

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The settings for H3-02, H3-06, and H3-10 [MFAI Function Select] and H7-30 [Virtual Analog Input Selection] overlap.

Corrective action

Set H3-02, H3-06, H3-10, and H7-30 correctly to prevent overlap.

— all from yaskawa.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.