Reference Source

oPE06 · GA800 · Parameter Setting Error

For oPE06 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE06; fault name is Control Method Selection Error; type is Parameter Setting Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
oPE06 verified
Fault name
Control Method Selection Error verified
Type
Parameter Setting Error verified
Cause
A1-02 = 1, 3, or 7 [Control Method Selection = CL- V/f, CLV, CLV/PM], but there is no encoder option connected the drive. verified
Corrective action
• Connect an encoder option the drive. • Set A1-02 correctly. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

oPE06 Control Method Selection Error Flashing Parameter Setting Error 137

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

A1-02 = 1, 3, or 7 [Control Method Selection = CL- V/f, CLV, CLV/PM], but there is no encoder option connected the drive.

Corrective action

• Connect an encoder option the drive. • Set A1-02 correctly.

— all from yaskawa.com, retrieved 2026-09-01