Reference Source

End9 · GA800 · Auto-Tuning Error

For End9, model / series is GA800; type is Auto-Tuning Error; brand is Yaskawa; fault name is Initial Pole Detection Alarm; cause is The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning, verified against its source on 2026-10-10.

Brand
Yaskawa
Model / series
GA800
Fault code
End9 verified
Fault name
Initial Pole Detection Alarm verified
Type
Auto-Tuning Error verified
Cause
The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning. verified
Corrective action
• Set the correct value on the motor nameplate E5-xx [PM motor parameters] or do Stationary/Rotational Auto-Tuning, and then do High Frequency Injection Tuning again. • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled], make sure that the motor does not rotate in reverse at start. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

End9 Initial Pole Detection Alarm Flashing Auto-Tuning Error 142

— yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning.

Corrective action

• Set the correct value on the motor nameplate E5-xx [PM motor parameters] or do Stationary/Rotational Auto-Tuning, and then do High Frequency Injection Tuning again. • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled], make sure that the motor does not rotate in reverse at start.

— all from yaskawa.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.