Reference Source

End9 · GA800 · Auto-Tuning Error

For End9 · GA800 · Auto-Tuning Error, brand is Yaskawa; model / series is GA800; fault code is End9; fault name is Initial Pole Detection Alarm; type is Auto-Tuning Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
End9 verified
Fault name
Initial Pole Detection Alarm verified
Type
Auto-Tuning Error verified
Cause
The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning. verified
Corrective action
• Set the correct value on the motor nameplate E5-xx [PM motor parameters] or do Stationary/Rotational Auto-Tuning, and then do High Frequency Injection Tuning again. • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled], make sure that the motor does not rotate in reverse at start. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

End9 Initial Pole Detection Alarm Flashing Auto-Tuning Error 142

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The drive cannot calculate the correct value for n8-84 [Polarity Detection Current] during High Frequency Injection Tuning.

Corrective action

• Set the correct value on the motor nameplate E5-xx [PM motor parameters] or do Stationary/Rotational Auto-Tuning, and then do High Frequency Injection Tuning again. • When n8-35 = 1 [Initial Pole Detection Method = High Frequency Injection] or n8-57 = 1 [HFI Overlap Selection = Enabled], make sure that the motor does not rotate in reverse at start.

— all from yaskawa.com, retrieved 2026-09-01

Source