CoF · GA800 · Fault

For CoF · GA800 · Fault, brand is Yaskawa; model / series is GA800; fault code is CoF; fault name is Current Offset Fault; type is Fault, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
CoF verified
Fault name
Current Offset Fault verified
Type
Fault verified
Cause
The drive starts operation while the induced voltage stays in the motor (during coasting to a stop or after fast deceleration). verified
Corrective action
• Make a sequence that does not restart operation when induced voltage stays in the motor. • Set b3-01 = 1 [Speed Search at Start Selection = Enabled]. • Use Speed Search from Fmax or Fref [H1-xx = 61, 62] to do a speed search through one of the external terminals. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

CoF (0046) Current Offset Fault Illuminated Fault 94

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The drive starts operation while the induced voltage stays in the motor (during coasting to a stop or after fast deceleration).

Corrective action

• Make a sequence that does not restart operation when induced voltage stays in the motor. • Set b3-01 = 1 [Speed Search at Start Selection = Enabled]. • Use Speed Search from Fmax or Fref [H1-xx = 61, 62] to do a speed search through one of the external terminals.

— all from yaskawa.com, retrieved 2026-09-01