71 · FC 301/302 · ALARM

For 71 · FC 301/302 · ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 71; fault name is PTC 1 safe stop; type is ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
71 verified
Fault name
PTC 1 safe stop verified
Type
ALARM verified
Cause
STO has been activated from the VLT® PTC Thermistor Card MCB 112 (motor too warm). Normal operation can be resumed when the MCB 112 applies 24 V DC to terminal 37 again (when the motor temperature reaches an acceptable level), and when the digital input from the MCB 112 is deactivated. When that happens, send a reset signal (via bus or digital I/O, or press [Reset]). verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

ALARM 71, PTC 1 safe stop

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

The value above is stated away from the sentence quoted with the answer, so the passage that states it is shown here too.

Cause

STO has been activated from the VLT® PTC Thermistor Card MCB 112 (motor too warm). Normal operation can be resumed when the MCB 112 applies 24 V DC to terminal 37 again (when the motor temperature reaches an acceptable level), and when the digital input from the MCB 112 is deactivated. When that happens, send a reset signal (via bus or digital I/O, or press [Reset]).

— all from files.danfoss.com, retrieved 2026-09-01