Reference Source

72 · FC 301/302 · ALARM

For 72 · FC 301/302 · ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 72; fault name is Dangerous failure; type is ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
72 verified
Fault name
Dangerous failure verified
Type
ALARM verified
Cause
STO with trip lock. An unexpected combination of STO commands has occurred: • VLT® PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled. • MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 1 warning in parameter 5-19 Terminal 37 Safe Stop), STO is activated, and X44/10 is not activated. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

ALARM 72, Dangerous failure

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

The value above is stated away from the sentence quoted with the answer, so the passage that states it is shown here too.

Cause

STO with trip lock. An unexpected combination of STO commands has occurred: • VLT® PTC Thermistor Card MCB 112 enables X44/10, but STO is not enabled. • MCB 112 is the only device using STO (specified through selection [4] PTC 1 alarm or [5] PTC 1 warning in parameter 5-19 Terminal 37 Safe Stop), STO is activated, and X44/10 is not activated.

— all from files.danfoss.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.