For F7 · PowerFlex 40, brand is Allen-Bradley; model / series is PowerFlex 40; fault code is F7; fault name is Motor Overload; cause is Internal electronic overload trip, verified against its source on 2026-09-01.
- Brand
- Allen-Bradley
- Model / series
- PowerFlex 40
- Fault code
- F7 verified
- Fault name
- Motor Overload verified
- Cause
- Internal electronic overload trip. verified
- Corrective action
- 1. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. 2. Verify A084 [Boost Select] setting verified
Verified
Review by
What the source says
F7 Motor Overload
— literature.rockwellautomation.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
Internal electronic overload trip.
Corrective action
1. An excessive motor load exists. Reduce load so drive output current does not exceed the current set by parameter P033 [Motor OL Current]. 2. Verify A084 [Boost Select] setting
— all from literature.rockwellautomation.com, retrieved 2026-09-01