F6 · PowerFlex 40

For F6 · PowerFlex 40, brand is Allen-Bradley; model / series is PowerFlex 40; fault code is F6; fault name is Motor Stalled; cause is Drive is unable to accelerate motor, verified against its source on 2026-09-01.

Brand
Allen-Bradley
Model / series
PowerFlex 40
Fault code
F6 verified
Fault name
Motor Stalled verified
Cause
Drive is unable to accelerate motor. verified
Corrective action
Increase P039…A067 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit 1]. verified
Sourceliterature.rockwellautomation.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

F6 Motor Stalled

literature.rockwellautomation.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

Drive is unable to accelerate motor.

Corrective action

Increase P039…A067 [Accel Time x] or reduce load so drive output current does not exceed the current set by parameter A089 [Current Limit 1].

— all from literature.rockwellautomation.com, retrieved 2026-09-01