Reference Source

End1 · GA800 · Auto-Tuning Error

For End1 · GA800 · Auto-Tuning Error, brand is Yaskawa; model / series is GA800; fault code is End1; fault name is Excessive Rated Voltage Setting; type is Auto-Tuning Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
End1 verified
Fault name
Excessive Rated Voltage Setting verified
Type
Auto-Tuning Error verified
Cause
The torque reference was more than 20% during Auto-Tuning or the no-load current that was measured after Auto-Tuning is more than 80%. verified
Corrective action
• Make sure that the input motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data. • If you can uncouple the motor and load, remove the motor from the machine and do Rotational Auto-Tuning again. • If you cannot uncouple the motor and load, use the results from Auto-Tuning. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

End1 Excessive Rated Voltage Setting Flashing Auto-Tuning Error 141

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The torque reference was more than 20% during Auto-Tuning or the no-load current that was measured after Auto-Tuning is more than 80%.

Corrective action

• Make sure that the input motor nameplate data is correct. • Do Auto-Tuning again and correctly set the motor nameplate data. • If you can uncouple the motor and load, remove the motor from the machine and do Rotational Auto-Tuning again. • If you cannot uncouple the motor and load, use the results from Auto-Tuning.

— all from yaskawa.com, retrieved 2026-09-01

Source