LSo · GA800 · Fault
For LSo · GA800 · Fault, brand is Yaskawa; model / series is GA800; fault code is LSo; fault name is Low Speed Motor Step-Out; type is Fault, verified against its source on 2026-09-01.
- Brand
- Yaskawa
- Model / series
- GA800
- Fault code
- LSo verified
- Fault name
- Low Speed Motor Step-Out verified
- Type
- Fault verified
- Cause
- The motor code set incorrectly. verified
- Corrective action
- • Set E5-01 [PM Motor Code Selection] correctly as specified by the motor. • For specialized motors, refer to the motor test report and set E5- xx correctly. verified
What the source says
LSo (0051) Low Speed Motor Step-Out Illuminated Fault 105
— yaskawa.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
The motor code set incorrectly.
Corrective action
• Set E5-01 [PM Motor Code Selection] correctly as specified by the motor. • For specialized motors, refer to the motor test report and set E5- xx correctly.
— all from yaskawa.com, retrieved 2026-09-01
Source
- yaskawa.comhttps://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAIGA8001&cmd=documents&documentName=TOEPYAIGA8001.pdf