Reference Source

oPE09 · GA800 · Parameter Setting Error

For oPE09 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE09; fault name is PID Control Selection Fault; type is Parameter Setting Error, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
oPE09 verified
Fault name
PID Control Selection Fault verified
Type
Parameter Setting Error verified
Cause
These parameters are set at the same time: • b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz] • b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer] • Set b5-15 ≠ 0.0. verified
Corrective action
• Set b1-03 = 0, 1 [Ramp to Stop, Coast to Stop]. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

oPE09 PID Control Selection Fault Flashing Parameter Setting Error 138

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

These parameters are set at the same time: • b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz] • b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer] • Set b5-15 ≠ 0.0.

Corrective action

• Set b1-03 = 0, 1 [Ramp to Stop, Coast to Stop].

— all from yaskawa.com, retrieved 2026-09-01

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.