oPE09 · GA800 · Parameter Setting Error
For oPE09 · GA800 · Parameter Setting Error, brand is Yaskawa; model / series is GA800; fault code is oPE09; fault name is PID Control Selection Fault; type is Parameter Setting Error, verified against its source on 2026-09-01.
- Brand
- Yaskawa
- Model / series
- GA800
- Fault code
- oPE09 verified
- Fault name
- PID Control Selection Fault verified
- Type
- Parameter Setting Error verified
- Cause
- These parameters are set at the same time: • b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz] • b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer] • Set b5-15 ≠ 0.0. verified
- Corrective action
- • Set b1-03 = 0, 1 [Ramp to Stop, Coast to Stop]. verified
What the source says
oPE09 PID Control Selection Fault Flashing Parameter Setting Error 138
— yaskawa.com, retrieved 2026-09-01
Where each value comes from
This source states these in separate places, so each value is shown with the passage that states it.
Cause
These parameters are set at the same time: • b5-15 ≠ 0.0 [PID Sleep Function Start Level ≠ 0.0 Hz] • b1-03 = 2, 3 [Stopping Method Selection = DC Injection Braking to Stop, Coast to Stop with Timer] • Set b5-15 ≠ 0.0.
Corrective action
• Set b1-03 = 0, 1 [Ramp to Stop, Coast to Stop].
— all from yaskawa.com, retrieved 2026-09-01
Source
- yaskawa.comhttps://www.yaskawa.com/delegate/getAttachment?documentId=TOEPYAIGA8001&cmd=documents&documentName=TOEPYAIGA8001.pdf