Reference Source

43 · FC 301/302 · ALARM

For 43 · FC 301/302 · ALARM, brand is Danfoss; model / series is FC 301/302; fault code is 43; fault name is Ext. supply; type is ALARM, verified against its source on 2026-09-01.

Brand
Danfoss
Model / series
FC 301/302
Fault code
43 verified
Fault name
Ext. supply verified
Type
ALARM verified
Cause
VLT® Extended Relay Option MCB 113 is mounted without external 24 V DC. Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle. verified
Sourcefiles.danfoss.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

ALARM 43, Ext. supply

files.danfoss.com, retrieved 2026-09-01

Where each value comes from

The value above is stated away from the sentence quoted with the answer, so the passage that states it is shown here too.

Cause

VLT® Extended Relay Option MCB 113 is mounted without external 24 V DC. Either connect a 24 V DC external supply or specify that no external supply is used via parameter 14-80 Option Supplied by External 24VDC, [0] No. A change in parameter 14-80 Option Supplied by External 24VDC requires a power cycle.

— all from files.danfoss.com, retrieved 2026-09-01