oL5 · GA800 · Fault

For oL5 · GA800 · Fault, brand is Yaskawa; model / series is GA800; fault code is oL5; fault name is Mechanical Weakening Detection 1; type is Fault, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
oL5 verified
Fault name
Mechanical Weakening Detection 1 verified
Type
Fault verified
Cause
The drive detected overtorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select]. verified
Corrective action
Do a deterioration diagnostic test on the machine side. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

oL5 (0044) Mechanical Weakening Detection 1 Illuminated Fault 117

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The drive detected overtorque as specified by the conditions for mechanical weakening detection set in L6-08 [Mechanical Fatigue Detect Select].

Corrective action

Do a deterioration diagnostic test on the machine side.

— all from yaskawa.com, retrieved 2026-09-01