For oH · GA800 · Fault, brand is Yaskawa; model / series is GA800; fault code is oH; fault name is Heatsink Overheat; type is Fault, verified against its source on 2026-09-01.

Brand
Yaskawa
Model / series
GA800
Fault code
oH verified
Fault name
Heatsink Overheat verified
Type
Fault verified
Cause
The ambient temperature is high and the heatsink temperature of the drive is more than the value set in L8-02 [Overheat Alarm Level]. verified
Corrective action
• Measure the ambient temperature. • Increase the airflow in the control panel. • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature. • Remove objects near the drive that are producing too much heat. verified
Sourceyaskawa.com
Verified
Review by
DatasetIndustrial VFD fault and alarm codes by brand

What the source says

oH (0009) Heatsink Overheat Illuminated Fault 114

yaskawa.com, retrieved 2026-09-01

Where each value comes from

This source states these in separate places, so each value is shown with the passage that states it.

Cause

The ambient temperature is high and the heatsink temperature of the drive is more than the value set in L8-02 [Overheat Alarm Level].

Corrective action

• Measure the ambient temperature. • Increase the airflow in the control panel. • Install a cooling device (cooling fan or air conditioner) to lower the ambient temperature. • Remove objects near the drive that are producing too much heat.

— all from yaskawa.com, retrieved 2026-09-01