US AIM Act sector-specific refrigerant GWP limits and compliance dates (40 CFR 84.54)

Federal sector-specific maximum GWP values for refrigerants and HFC-containing products under the AIM Act Technology Transitions rule (40 CFR 84.54). Each record is one sector/subsector with the GWP ceiling, the effective date for manufacture/import restrictions, the effective date for installation restrictions (often different), equipment size or temperature conditions, and any exemptions. Answers 'what is the maximum GWP refrigerant I can use in a new supermarket system?', 'when does the R-410A ban take effect for residential AC?', 'is there an exemption for semiconductor manufacturing chillers?', and 'what changed in the May 2026 reconsideration rule?' — questions where the answer depends on the sector, the date, the equipment size, and the temperature range, and where assistants typically give the residential AC answer (700 GWP) regardless of the sector.

Records71
Sources1
Verified2026-08-06
Review by2027-02-02
LicenceUS federal regulation, public domain. 40 CFR Part 84 is government work published at ecfr.gov.

The data

Sector/subsectorRestriction typeMaximum GWPEffective dateCFR paragraphConditionsExemptions
self-contained residential and light commercial air conditioning and heat pump productsmanufacture/import700January 1, 2025§ 84.54(a)(1)
chillers for comfort coolingmanufacture/import700January 1, 2025§ 84.54(a)(10)(i)when a stand-alone product
chillers for ice rinksmanufacture/import700January 1, 2025§ 84.54(a)(10)(ii)when a stand-alone product
chillers for industrial process refrigerationmanufacture/import700January 1, 2026§ 84.54(a)(10)(iii)where the temperature of the fluid exiting the chiller is greater than −22 °F (−30 °C)
chillers for industrial process refrigerationmanufacture/import700January 1, 2028§ 84.54(a)(10)(iv)where the temperature of the fluid exiting the chiller is greater than or equal to −50 °C (−58 °F) and less than or equal to −30 °C (−22 °F)
Chillersmanufacture/importJanuary 1, 2030§ 84.54(a)(10)(v)with a refrigerant charge capacity of 100 pounds or less that are used in the manufacture of semiconductors
self-contained products in data center, information technology equipment facility, and computer room coolingmanufacture/import700January 1, 2027§ 84.54(a)(11)
Industrial process refrigeration products, other than chillersmanufacture/import150January 1, 2026§ 84.54(a)(12)(i)with a refrigerant charge capacity of 200 pounds or greater and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F)
Industrial process refrigeration products, other than chillersmanufacture/import300January 1, 2026§ 84.54(a)(12)(ii)with a refrigerant charge capacity less than 200 pounds and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F)
Industrial process refrigeration products, other than chillersmanufacture/import700January 1, 2028§ 84.54(a)(12)(iii)where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F)
Industrial process refrigeration products, other than chillersmanufacture/importJanuary 1, 2030§ 84.54(a)(12)(iv)with a refrigerant charge capacity of 100 pounds or less that are used in the manufacture of semiconductors
Refrigerated centrifuges and laboratory shaker tablesmanufacture/importJanuary 1, 2028§ 84.54(a)(12)(v)
Motor vehicle air-conditioningmanufacture/import150October 24, 2024§ 84.54(a)(13)(i)for Model Year 2025 and subsequent model year light-duty passenger cars and trucks (vehicles with a gross vehicle weight rating less than 8,500 lb)
Motor vehicle air-conditioningmanufacture/import150Model Year 2028§ 84.54(a)(13)(ii)medium-duty passenger vehicles, heavy-duty pick-up trucks, and complete heavy-duty vans, as defined by the Federal Highway Administration
Motor vehicle air-conditioningmanufacture/import150January 1, 2028§ 84.54(a)(13)(iii)certain nonroad vehicles (agricultural tractors greater than 40 horsepower; self-propelled agricultural machinery; compact equipment; construction, forestry, and mining equipment; and commercial utility vehicles)
Rigid polyurethane appliance foam, commercial refrigeration foam, laminated boardstock, marine flotation foam, sandwich panels, and slabstockmanufacture/import150January 1, 2025§ 84.54(a)(14)(i)foam products
Flexible polyurethanemanufacture/import150January 1, 2025§ 84.54(a)(14)(ii)foam products
Integral skin polyurethanemanufacture/import150January 1, 2025§ 84.54(a)(14)(iii)foam products
Polystyrene—extruded boardstock, billet, and extruded sheetmanufacture/import150January 1, 2025§ 84.54(a)(14)(iv)foam products
Phenolic insulation board and bunstockmanufacture/import150January 1, 2025§ 84.54(a)(14)(v)foam products
Polyisocyanurate laminated boardstockmanufacture/import150January 1, 2025§ 84.54(a)(14)(vi)foam products
Polyolefinmanufacture/import150January 1, 2025§ 84.54(a)(14)(vii)foam products
Rigid polyurethane spray foammanufacture/import150January 1, 2025§ 84.54(a)(14)(viii)foam products
foam productsmanufacture/importJanuary 1, 2026§ 84.54(a)(15)for use in space and military applicationsexcept spray and pour foams that are for use in space vehicles
Aerosol productsmanufacture/import150January 1, 2025§ 84.54(a)(16)(i)except products that use HFC-43-10mee (1,1,1,2,3,4,4,5,5,5-pentafluoropentane) or HFC-245fa (1,1,1,3,3-pentafluoropropane) as an aerosol solvent
aerosol productsmanufacture/import150January 1, 2028§ 84.54(a)(16)(ii)except defense sprays
residential dehumidifiersmanufacture/import700January 1, 2025§ 84.54(a)(2)
household refrigerators and freezersmanufacture/import150January 1, 2025§ 84.54(a)(3)
retail food refrigeration—stand-alone unitsmanufacture/import150January 1, 2025§ 84.54(a)(4)
vending machinesmanufacture/import150January 1, 2025§ 84.54(a)(5)
refrigerated transport—intermodal containersmanufacture/import700July 27, 2026§ 84.54(a)(6)with a box temperature of −35 °C (−31 °F) or higher
self-contained products in refrigerated transport—road and refrigerated transport—marine subsectorsmanufacture/importnamed listJanuary 1, 2025§ 84.54(a)(7)R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation) or GHG-X5
Self-contained automatic commercial ice machinesmanufacture/import150January 1, 2026§ 84.54(a)(8)(i)(A)with a harvest rate less than or equal to 1,000 pounds of ice per 24 hours
Self-contained automatic commercial ice machinesmanufacture/import150January 1, 2026§ 84.54(a)(8)(i)(B)with a harvest rate less than or equal to 1,200 pounds of ice per 24 hours
batch type ice maker productsmanufacture/importnamed listJanuary 1, 2027§ 84.54(a)(8)(ii)with a harvest rate greater than 1,000 pounds of ice per 24 hours
continuous type ice machine productsmanufacture/importnamed listJanuary 1, 2027§ 84.54(a)(8)(ii)with a harvest rate greater than 1,200 pounds of ice per 24 hours
Self-contained refrigerated food processing and dispensing productsmanufacture/import150January 1, 2027§ 84.54(a)(9)(i)with refrigerant charge sizes less than or equal to 500 g
Self-contained refrigerated food processing and dispensing productsmanufacture/importnamed listJanuary 1, 2027§ 84.54(a)(9)(ii)with refrigerant charge sizes greater than 500 g
refrigerated food processing and dispensing productsmanufacture/importnamed listJanuary 1, 2028§ 84.54(a)(9)(iii)within the scope of UL 621
any product that uses a regulated substance as listed in paragraph (a)sale/distributionthree years after the dates listed for each subsector§ 84.54(b)
residential or light commercial air-conditioning or heat pump systemsinstallation700January 1, 2025§ 84.54(c)(1)may continue to be installed where all specified components of that system are manufactured or imported prior to January 1, 2025except for variable refrigerant flow air-conditioning and heat pump systems
Industrial process refrigeration systems, other than chiller systemsinstallation150January 1, 2026§ 84.54(c)(10)(i)systems with a refrigerant charge capacity of 200 pounds or greater and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F), that are not the high temperature side of a cascade system
Industrial process refrigeration systems, other than chiller systemsinstallation300January 1, 2026§ 84.54(c)(10)(ii)systems with a refrigerant charge capacity less than 200 pounds and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F)
Industrial process refrigeration systems, other than chiller systemsinstallation300January 1, 2026§ 84.54(c)(10)(iii)the high temperature side of cascade systems with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F)
Industrial process refrigeration systems, other than chiller systemsinstallation700January 1, 2028§ 84.54(c)(10)(iv)where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F)
Systems used in the manufacture of semiconductorsinstallationJanuary 1, 2030§ 84.54(c)(10)(v)with a charge size of 100 pounds or less
remote condensing units in retail food refrigeration systemsinstallation1,400July 27, 2026§ 84.54(c)(11)(i)
remote condensing units in retail food refrigeration systemsinstallation150January 1, 2032§ 84.54(c)(11)(ii)(A)Systems with a refrigerant charge capacity of 200 pounds or greater, that are not the high temperature side of a cascade system
remote condensing units in retail food refrigeration systemsinstallation300January 1, 2032§ 84.54(c)(11)(ii)(B)Systems with a refrigerant charge capacity less than 200 pounds
remote condensing units in retail food refrigeration systemsinstallation300January 1, 2032§ 84.54(c)(11)(ii)(C)Cascade refrigerant systems using a regulated substance, or a blend containing a regulated substance, on the high temperature side of the system
supermarket systemsinstallation1,400January 1, 2027§ 84.54(c)(12)(i)
supermarket systemsinstallation150January 1, 2032§ 84.54(c)(12)(ii)(A)Systems with a refrigerant charge capacity of 200 pounds or greater, that are not the high temperature side of a cascade system
supermarket systemsinstallation300January 1, 2032§ 84.54(c)(12)(ii)(B)Systems with a refrigerant charge capacity less than 200 pounds
supermarket systemsinstallation300January 1, 2032§ 84.54(c)(12)(ii)(C)Cascade refrigerant systems using a regulated substance, or a blend containing a regulated substance, on the high temperature side of the system
data center, information technology equipment facility, and computer room cooling systemsinstallation700January 1, 2027§ 84.54(c)(13)
automatic commercial ice machines with a remote condenserinstallationnamed listJanuary 1, 2027§ 84.54(c)(14)R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), or GHG-X5
refrigerated food processing and dispensing equipment with a remote condenserinstallationnamed listJanuary 1, 2027§ 84.54(c)(15)R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, or Freeze 12
variable refrigerant flow systems for use as residential or light commercial air-conditioning or heat pumpsinstallation700January 1, 2026§ 84.54(c)(2)may be installed prior to January 1, 2027, where all specified components of that system are manufactured or imported prior to January 1, 2026may be installed prior to January 1, 2028, when an approved building permit issued prior to October 5, 2023, specifies the use of a restricted regulated substance
chillers for comfort coolinginstallation700January 1, 2025§ 84.54(c)(3)
ice rinksinstallation700January 1, 2025§ 84.54(c)(4)
chillers for industrial process refrigerationinstallation700January 1, 2026§ 84.54(c)(5)(i)where the temperature of the fluid exiting the chiller is greater than -30 °C (−22 °F)
ChillersinstallationJanuary 1, 2030§ 84.54(c)(5)(ii)with a refrigerant charge capacity of 100 pounds or less that are used in the manufacture of semiconductors
chillers for industrial process refrigerationinstallation700January 1, 2028§ 84.54(c)(6)(i)where the temperature of the fluid exiting the chiller is greater than or equal to −50 °C (−58 °F) and less than or equal to −30 °C (−22 °F)
ChillersinstallationJanuary 1, 2030§ 84.54(c)(6)(ii)with a refrigerant charge capacity of 100 pounds or less that are used in the manufacture of semiconductors
refrigerated transport—intermodal containersinstallation700July 27, 2026§ 84.54(c)(7)with a box temperature of −35 °C (−31 °F) or higher
refrigerated transport—road or refrigerated transport—marine systemsinstallationnamed listJanuary 1, 2025§ 84.54(c)(8)R-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation) or GHG-X5
cold storage warehouse systemsinstallation700July 27, 2026§ 84.54(c)(9)(i)
cold storage warehouse systemsinstallation150January 1, 2032§ 84.54(c)(9)(ii)(A)Systems with a refrigerant charge capacity of 200 pounds or greater, that are not the high temperature side of a cascade system
cold storage warehouse systemsinstallation300January 1, 2032§ 84.54(c)(9)(ii)(B)Systems with a refrigerant charge capacity less than 200 pounds
cold storage warehouse systemsinstallation300January 1, 2032§ 84.54(c)(9)(ii)(C)Cascade refrigerant systems using a regulated substance, or a blend containing a regulated substance, on the high temperature side of the system
industrial process refrigeration systems with a January 1, 2026, compliance date, retail food—supermarket, cold storage warehouse, and ice rink subsectorsinstallationextended one year beyond the specified compliance date§ 84.54(d)when an approved building permit issued prior to October 5, 2023, specifies the use of a restricted regulated substance