data center, information technology equipment facility, and computer room cooling systems

For data center, information technology equipment facility, and computer room cooling systems, restriction type is installation; maximum gwp is 700; effective date is January 1, 2027; cfr paragraph is § 84.54(c)(13), recorded from its source on 2026-08-06.

Sector/subsector
data center, information technology equipment facility, and computer room cooling systems verified
Restriction type
installation our reading
Maximum GWP
700 verified
Effective date
January 1, 2027 verified
CFR paragraph
§ 84.54(c)(13) our reading
Sourceecfr.gov
Verified2026-08-06
Review by2027-02-02
DatasetUS AIM Act sector-specific refrigerant GWP limits and compliance dates (40 CFR 84.54)

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

( 13 ) Effective January 1, 2027, data center, information technology equipment facility, and computer room cooling systems using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 700 or greater;

ecfr.gov, retrieved 2026-08-06