Reference Source

Industrial process refrigeration products, other than chillers

For Industrial process refrigeration products, other than chillers, restriction type is manufacture/import; maximum gwp is 700; effective date is January 1, 2028; conditions is where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F); cfr paragraph is § 84.54(a)(12)(iii), recorded from its source on 2026-08-06.

Sector/subsector
Industrial process refrigeration products, other than chillers verified
Restriction type
manufacture/import our reading
Maximum GWP
700 verified
Effective date
January 1, 2028 verified
Conditions
where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F) verified
CFR paragraph
§ 84.54(a)(12)(iii) our reading
Sourceecfr.gov
Verified2026-08-06
Review by2027-02-02
DatasetUS AIM Act sector-specific refrigerant GWP limits and compliance dates (40 CFR 84.54)

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

( 12 ) Industrial process refrigeration products, other than chillers, as follows: ( i ) Effective January 1, 2026, products with a refrigerant charge capacity of 200 pounds or greater and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F) using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 150 or greater; ( ii ) Effective January 1, 2026, products with a refrigerant charge capacity less than 200 pounds and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F), using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 300 or greater; ( iii ) Effective January 1, 2028, where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F), using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 700 or greater;

ecfr.gov, retrieved 2026-08-06

Source

Last verified against source: 2026-08-06. Due for re-check by 2027-02-02. This page as Markdown · OKF bundle · full dataset as JSON.