Industrial process refrigeration systems, other than chiller systems

For Industrial process refrigeration systems, other than chiller systems, restriction type is installation; maximum gwp is 700; effective date is January 1, 2028; conditions is where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F); cfr paragraph is § 84.54(c)(10)(iv), recorded from its source on 2026-08-06.

Sector/subsector
Industrial process refrigeration systems, other than chiller systems verified
Restriction type
installation our reading
Maximum GWP
700 verified
Effective date
January 1, 2028 verified
Conditions
where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F) verified
CFR paragraph
§ 84.54(c)(10)(iv) our reading
Sourceecfr.gov
Verified2026-08-06
Review by2027-02-02
DatasetUS AIM Act sector-specific refrigerant GWP limits and compliance dates (40 CFR 84.54)

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

( 10 ) Industrial process refrigeration systems, other than chiller systems, as follows: ( i ) Effective January 1, 2026, systems with a refrigerant charge capacity of 200 pounds or greater and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F), that are not the high temperature side of a cascade system, using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 150 or greater; ( ii ) Effective January 1, 2026, systems with a refrigerant charge capacity less than 200 pounds and with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F), using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 300 or greater; ( iii ) Effective January 1, 2026, the high temperature side of cascade systems with the refrigerant temperature entering the evaporator higher than −30 °C (−22 °F) using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 300 or greater; ( iv ) Effective January 1, 2028, where the temperature of the refrigerant entering the evaporator is greater than or equal to −50 °C (−58 °F) and is less than or equal to −30 °C (−22 °F), using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 700 or greater; and

ecfr.gov, retrieved 2026-08-06