supermarket systems · installation · § 84.54(c)(12)(ii)(B)
What is the maximum gwp for supermarket systems · installation · § 84.54(c)(12)(ii)(B)?
For supermarket systems, restriction type is installation; cfr paragraph is § 84.54(c)(12)(ii)(B); maximum gwp is 300; effective date is January 1, 2032; conditions is Systems with a refrigerant charge capacity less than 200 pounds, recorded from its source on 2026-08-06.
(ii) Effective January 1, 2032, supermarket systems using a regulated substance, or a blend containing a regulated substance, as follows: (A) Systems with a refrigerant charge capacity of 200 pounds or greater, that are not the high temperature side of a cascade system, using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 150 or greater; (B) Systems with a refrigerant charge capacity less than 200 pounds using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 300 or greater; and
— ecfr.gov, retrieved 2026-08-06
- Sector/subsector
- supermarket systems verified
- Restriction type
- installation our reading
- Maximum GWP
- 300 verified
- Effective date
- January 1, 2032 verified
- Conditions
- Systems with a refrigerant charge capacity less than 200 pounds verified
- CFR paragraph
- § 84.54(c)(12)(ii)(B) our reading
Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.