chillers for industrial process refrigeration
For chillers for industrial process refrigeration, restriction type is installation; maximum gwp is 700; effective date is January 1, 2028; conditions is where the temperature of the fluid exiting the chiller is greater than or equal to −50 °C (−58 °F) and less than or equal to −30 °C (−22 °F); cfr paragraph is § 84.54(c)(6)(i), recorded from its source on 2026-08-06.
- Sector/subsector
- chillers for industrial process refrigeration verified
- Restriction type
- installation our reading
- Maximum GWP
- 700 verified
- Effective date
- January 1, 2028 verified
- Conditions
- where the temperature of the fluid exiting the chiller is greater than or equal to −50 °C (−58 °F) and less than or equal to −30 °C (−22 °F) verified
- CFR paragraph
- § 84.54(c)(6)(i) our reading
Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.
What the source says
( i ) Effective January 1, 2028, chillers for industrial process refrigeration where the temperature of the fluid exiting the chiller is greater than or equal to −50 °C (−58 °F) and less than or equal to −30 °C (−22 °F) using a regulated substance, or a blend containing a regulated substance, with a global warming potential of 700 or greater; and
— ecfr.gov, retrieved 2026-08-06
Source
- ecfr.govhttps://www.ecfr.gov/current/title-40/chapter-I/subchapter-C/part-84