Nevada
For Nevada, governing body is Department of Business & Industry, Division of Industrial Relations, Mechanical Compliance Section; statute citation is Nevada Administrative Code, Title 455C. Boilers, Elevators, and Pressure Vessels; power boiler inspection interval is One annual internal inspection; One annual external inspection at approximately a six-month interval from the internal inspection; low-pressure boiler inspection interval is Low-pressure steam heating boilers: one annual external inspection. Where design and construction permit, an internal inspection shall be conducted biennially. Hot-water heating boilers and hot-water supply boilers: one internal inspection biennially if design and construction permit and inspector/special inspector requests it or external including operational testing of all controls and safety devices. Lined potable water heaters: one biennial external inspection including operational testing of all controls and safety devices; pressure vessel inspection interval is Mechanical Compliance Section jurisdiction: One external inspection quadrennially; internal if design and construction permit. Mine Section jurisdiction: One external inspection triennially; internal if design and construction permit, recorded from its source on 2026-08-05.
- State
- Nevada
- Governing body
- Department of Business & Industry, Division of Industrial Relations, Mechanical Compliance Section unconfirmed
- Statute citation
- Nevada Administrative Code, Title 455C. Boilers, Elevators, and Pressure Vessels
- Power boiler inspection interval
- One annual internal inspection; One annual external inspection at approximately a six-month interval from the internal inspection. unconfirmed
- Low-pressure boiler inspection interval
- Low-pressure steam heating boilers: one annual external inspection. Where design and construction permit, an internal inspection shall be conducted biennially. Hot-water heating boilers and hot-water supply boilers: one internal inspection biennially if design and construction permit and inspector/special inspector requests it or external including operational testing of all controls and safety devices. Lined potable water heaters: one biennial external inspection including operational testing of all controls and safety devices. unconfirmed
- Pressure vessel inspection interval
- Mechanical Compliance Section jurisdiction: One external inspection quadrennially; internal if design and construction permit. Mine Section jurisdiction: One external inspection triennially; internal if design and construction permit. unconfirmed
- Accepted inspector types
- An inspection made by a special inspector (employed by an inspection entity), holding a Certificate of Competency received from the division, is accepted in lieu of an inspection made by a Jurisdictional inspector. unconfirmed
- Exemptions
- Objects meeting exemption rules per NAC 455C.114 unconfirmed
Values marked unconfirmed are shown, but we could not tie them to the quote below: Accepted inspector types, Exemptions, Governing body, Low-pressure boiler inspection interval, Power boiler inspection interval, Pressure vessel inspection interval. Read the quote and judge them yourself.
What the source says
Nevada Administrative Code, Title 455C. Boilers, Elevators, and Pressure Vessels Mine Section:
— nationalboard.org, retrieved 2026-08-05
Source
- nationalboard.orghttps://www.nationalboard.org/PrintAllSynopsis.aspx?Jurisdiction=Select