Montana

For Montana, governing body is Department of Labor and Industry, Building Codes Bureau, Boiler, Elevator, Weights and Measures; statute citation is Montana Code 2001, Title 50. Health and Safety, Chapter 60. Building Construction Standards and Chapter 74. Boiler and Steam Engines; power boiler inspection interval is Steam heating and power boilers: annual internal inspection. All manually-fired boilers and all boilers and banks of boilers rated with a total input of 400,000 BTU per hour or greater: annual inspection; low-pressure boiler inspection interval is All automatically fired boilers rated with an input of less than 400,000 BTU per hour: biennial inspection; accepted inspector types is Inspections made by inspectors employed by insurance companies may be accepted in lieu of inspections made by bureau inspectors as equivalent to those of the state inspectors. Each such special inspector shall hold a certificate as boiler inspector issued by the National Board of Boiler and Pressure Vessel Inspectors, recorded from its source on 2026-08-05.

State
Montana
Governing body
Department of Labor and Industry, Building Codes Bureau, Boiler, Elevator, Weights and Measures
Statute citation
Montana Code 2001, Title 50. Health and Safety, Chapter 60. Building Construction Standards and Chapter 74. Boiler and Steam Engines.
Power boiler inspection interval
Steam heating and power boilers: annual internal inspection. All manually-fired boilers and all boilers and banks of boilers rated with a total input of 400,000 BTU per hour or greater: annual inspection. verified
Low-pressure boiler inspection interval
All automatically fired boilers rated with an input of less than 400,000 BTU per hour: biennial inspection. verified
Accepted inspector types
Inspections made by inspectors employed by insurance companies may be accepted in lieu of inspections made by bureau inspectors as equivalent to those of the state inspectors. Each such special inspector shall hold a certificate as boiler inspector issued by the National Board of Boiler and Pressure Vessel Inspectors.
Exemptions
Boilers under federal control. Steam-heating boilers operated at not over 15 psig in private residences or apartments of six or fewer families. Hot-water heating or supply boilers operated at not over 50 psig and temperatures not over 250°F when in private residences, or apartments of six or fewer families.
Sourcenationalboard.org
Verified2026-08-05
Review by2027-08-05
DatasetUS boiler and pressure vessel inspection requirements by state

What the source says

All manually-fired boilers and all boilers and banks of boilers rated with a total input of 400,000 BTU per hour or greater: annual inspection. All automatically fired boilers rated with an input of less than 400,000 BTU per hour: biennial inspection. Steam heating and power boilers: annual internal inspection. This inspection may be performed during a scheduled maintenance shutdown with prior approval from the department. If located in a school, day-care center, hospital, rest home, retirement center, or place of assembly with a capacity of more than 100 persons: an annual inspection is required.

nationalboard.org, retrieved 2026-08-05

Source

Last verified against source: 2026-08-05. Due for re-check by 2027-08-05. This page as Markdown · OKF bundle · full dataset as JSON.