Reference Source

California

For California, governing body is Department of Industrial Relations, Division of Industrial Safety and Health; statute citation is California Code of Regulations, Title 8. Chapter 4. Division of Industrial Safety, Subchapter 1. Unfired Pressure Vessel Safety , Sections 450 through 560; Subchapter 2. Boiler and Fired Pressure Vessel Safety , Sections 750 through 797; power boiler inspection interval is one annual internal and external inspection (Exception: boilers in turbo-electric plants furnishing steam to a single turbine inspected internally at least once each 18 months); Title 8, Section 770 allows fired boilers to go up to three years without internal inspection after application and acceptance by the Pressure Vessel Unit; pressure vessel inspection interval is one inspection at least every three years for portable air tanks and five years for all other air tanks; LPG tanks on schedule by usage type (3–5 years); accepted inspector types is Inspectors holding a valid Certificate of Competency issued by the division (accepted in lieu of Pressure Vessel Unit engineer); owner/user organization inspectors whose inservice programs have been approved by the Pressure Vessel Unit, recorded from its source on 2026-08-05.

State
California verified
Governing body
Department of Industrial Relations, Division of Industrial Safety and Health
Statute citation
California Code of Regulations, Title 8. Chapter 4. Division of Industrial Safety, Subchapter 1. Unfired Pressure Vessel Safety , Sections 450 through 560; Subchapter 2. Boiler and Fired Pressure Vessel Safety , Sections 750 through 797. verified
Power boiler inspection interval
one annual internal and external inspection (Exception: boilers in turbo-electric plants furnishing steam to a single turbine inspected internally at least once each 18 months); Title 8, Section 770 allows fired boilers to go up to three years without internal inspection after application and acceptance by the Pressure Vessel Unit
Pressure vessel inspection interval
one inspection at least every three years for portable air tanks and five years for all other air tanks; LPG tanks on schedule by usage type (3–5 years)
Accepted inspector types
Inspectors holding a valid Certificate of Competency issued by the division (accepted in lieu of Pressure Vessel Unit engineer); owner/user organization inspectors whose inservice programs have been approved by the Pressure Vessel Unit
Exemptions
Boilers and pressure vessels under federal inspection and control or exempted by the labor code; boilers on automobiles and road motor vehicles; boilers and unfired pressure vessels used in household service; air pressure tanks under US DOT, Public Utilities Commission, or Highway Patrol jurisdiction; unfired pressure vessels not subject to more than 15 psi; unfired pressure vessels with inside diameter not exceeding 6 inches; small power boilers with automatic controls not exceeding 100 sq ft heating surface, 16-inch inside diameter steam drums, 100 psi MAWP, 35-gallon water capacity, 400,000 BTU/hr input; LP gas cylinders per US DOT; air tanks of 1-1/2 cubic feet or less not exceeding 150 psi
Sourcenationalboard.org
Verified2026-08-05
Review by2027-08-05
DatasetUS boiler and pressure vessel inspection requirements by state

What the source says

California Code of Regulations, Title 8. Chapter 4. Division of Industrial Safety, Subchapter 1. Unfired Pressure Vessel Safety , Sections 450 through 560; Subchapter 2. Boiler and Fired Pressure Vessel Safety , Sections 750 through 797. RULES FOR CONSTRUCTION AND STAMPING Construction:

nationalboard.org, retrieved 2026-08-05

Source

Last verified against source: 2026-08-05. Due for re-check by 2027-08-05. This page as Markdown · OKF bundle · full dataset as JSON.