stored pressure dry chemical extinguishers that require a 12-year hydrostatic test · Internal examination · OSHA 29 CFR 1910.157

For stored pressure dry chemical extinguishers that require a 12-year hydrostatic test · Internal examination · OSHA 29 CFR 1910.157, extinguishing agent / type is stored pressure dry chemical extinguishers that require a 12-year hydrostatic test; service obligation is Internal examination; interval is every 6 years; authority is OSHA 29 CFR 1910.157, recorded from its source on 2026-08-19.

Extinguishing agent / type
stored pressure dry chemical extinguishers that require a 12-year hydrostatic test verified
Service obligation
Internal examination our reading
Interval
every 6 years verified
Authority
OSHA 29 CFR 1910.157 our reading
Sourceecfr.gov
Verified
Review by
DatasetFire extinguisher inspection, maintenance and hydrostatic test intervals by agent type

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

The employer shall assure that stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and subjected to applicable maintenance procedures every 6 years. Dry chemical extinguishers having non-refillable disposable containers are exempt from this requirement. When recharging or hydrostatic testing is performed, the 6-year requirement begins from that date.

ecfr.gov, retrieved 2026-08-19

Source