Reference Source

Dry chemical, stored pressure · mild steel, brazed brass or aluminum shells · Hydrostatic test · OSHA 29 CFR 1910.157

For Dry chemical, stored pressure · mild steel, brazed brass or aluminum shells · Hydrostatic test · OSHA 29 CFR 1910.157, extinguishing agent / type is Dry chemical, stored pressure; shell material qualifier is mild steel, brazed brass or aluminum shells; service obligation is Hydrostatic test; interval is 12; authority is OSHA 29 CFR 1910.157, recorded from its source on 2026-08-19.

Extinguishing agent / type
Dry chemical, stored pressure verified
Shell material qualifier
mild steel, brazed brass or aluminum shells verified
Service obligation
Hydrostatic test our reading
Interval
12 verified
Authority
OSHA 29 CFR 1910.157 our reading
Section
Table L-1 verified
Sourceecfr.gov
Verified
Review by
DatasetFire extinguisher inspection, maintenance and hydrostatic test intervals by agent type

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threads are damaged; ( iii ) When there is corrosion that has caused pitting, including corrosion under removable name plate assemblies; ( iv ) When the extinguisher has been burned in a fire; or ( v ) When a calcium chloride extinguishing agent has been used in a stainless steel shell. ( 3 ) In addition to an external visual examination, the employer shall assure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests. Table L-1 Type of extinguishers | Test interval (years) | Soda acid (soldered brass shells) (until 1/1/82) | ( 1 ) | Soda acid (stainless steel shell) | 5 | Cartridge operated water and/or antifreeze | 5 | Stored pressure water and/or antifreeze | 5 | Wetting agent | 5 | Foam (soldered brass shells) (until 1/1/82) | ( 1 ) | Foam (stainless steel shell) | 5 | Aqueous Film Forming foam (AFFF) | 5 | Loaded stream | 5 | Dry chemical with stainless steel | 5 | Carbon dioxide | 5 | Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12

ecfr.gov, retrieved 2026-08-19

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.