Halon 1211 · Hydrostatic test · OSHA 29 CFR 1910.157
What is the interval for Halon 1211 · Hydrostatic test · OSHA 29 CFR 1910.157?
For Halon 1211, service obligation is Hydrostatic test; authority is OSHA 29 CFR 1910.157; interval is 12; section is Table L-1, recorded from its source on 2026-08-19.
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: (i) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; (ii) When the cylinder or shell threads are damaged; (iii) When there is corrosion that has caused pitting, including corrosion under removable name plate assemblies; (iv) When the extinguisher has been burned in a fire; or (v) When a calcium chloride extinguishing agent has been used in a stainless steel shell. (3) In addition to an external visual examination, the employer shall assure that an internal examination of cylinders and shells to be tested is made prior to the hydrostatic tests. Table L-1 Type of extinguishers | Test interval (years) | Soda acid (soldered brass shells) (until 1/1/82) | (1) | Soda acid (stainless steel shell) | 5 | Cartridge operated water and/or antifreeze | 5 | Stored pressure water and/or antifreeze | 5 | Wetting agent | 5 | Foam (soldered brass shells) (until 1/1/82) | (1) | Foam (stainless steel shell) | 5 | Aqueous Film Forming foam (AFFF) | 5 | Loaded stream | 5 | Dry chemical with stainless steel | 5 | Carbon dioxide | 5 | Dry chemical, stored pressure, with mild steel, brazed brass or aluminum shells | 12 | Dry chemical, cartridge or cylinder operated, with mild steel shells | 12 | Halon 1211 | 12
— ecfr.gov, retrieved 2026-08-19
- Extinguishing agent / type
- Halon 1211 verified
- Service obligation
- Hydrostatic test our reading
- Interval
- 12 verified
- Authority
- OSHA 29 CFR 1910.157 our reading
- Section
- Table L-1 verified
Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.
Source
- ecfr.govhttps://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157