Reference Source

T

For T, positive-leg alloy is Copper; negative-leg alloy is Constantan; ansi/astm positive-leg color is Blue; ansi/astm negative-leg color is Red; ansi extension-grade jacket color is Blue, verified against its source on 2026-08-19.

Type letter
T verified
Positive-leg alloy
Copper verified
Negative-leg alloy
Constantan verified
ANSI/ASTM positive-leg color
Blue verified
ANSI/ASTM negative-leg color
Red verified
ANSI extension-grade jacket color
Blue verified
Source document
ANSI/ASTM Thermocouple Color Codes verified
Usable temperature range
–270 to 400°C per assets.omega.com
IEC 60584 Class 1 tolerance
–40°C to +125°C ±0.5°C 125°C to 350°C ±0.004⋅ |t| per tc-inc.com
IEC 60584 Class 2 tolerance
–40°C to +133°C ±1.0°C 133°C to 350°C ±0.0075 ⋅ |t| per tc-inc.com
IEC 60584-3 positive-leg color
Brown per tc.co.uk
IEC 60584-3 negative-leg color
White per tc.co.uk
IEC 60584-3 outer sheath colour
Brown per tc.co.uk
Sourcethermometricscorp.com
Verified
Review by
DatasetThermocouple type letter to alloy pair, ANSI/IEC color code and tolerance class

What the source says

Type | Positive conductor | Negative conductor | Positive color | Negative color | Extension-grade jacket | Thermocouple-grade jacket shown in legacy assets | T | Copper | Constantan | Blue | Red | Blue | Brown |

thermometricscorp.com, retrieved 2026-08-19

Sources disagree

More than one authority states this, and they do not state the same thing. Both are reproduced with the source each came from — deciding between them is yours, not ours.

Source document

thermometricscorp.com says source document is ANSI/ASTM Thermocouple Color Codes, as of 2026-08-19.

Type | Positive conductor | Negative conductor | Positive color | Negative color | Extension-grade jacket | Thermocouple-grade jacket shown in legacy assets | T | Copper | Constantan | Blue | Red | Blue | Brown |

https://thermometricscorp.com/thermocouple-color-codes.html

assets.omega.com says source document is ANSI and IEC Color Codes, as of 2026-08-19.

Mild Oxidizing, + + + + T T CONSTANTAN Reducing Vacuum or – – COPPER COPPER- Inert. Good Where –270 to 400°C –6.258 to – – Cu Moisture Is Present. Low NICKEL Temperature & Cryogenic –454 to 752°F 20.872 Cu–Ni Applications

https://assets.omega.com/pdf/test-and-measurement-equipment/temperature/sensors/thermocouple-probes/tc_colorcodes.pdf

tc-inc.com says source document is Thermocouple Tolerances, as of 2026-08-19.

Thermocouple Output Tolerances to IEC 60584-1 | Type | + Leg | - Leg | 100ºC | 500ºC | 1000ºC | Continuous | Short Term | Type | Class 1 | Class 2 | K | NICKEL - CHROMIUM Also known as: Chromel™, Thermokanthal KP*, NiCr, T1*, Tophel™ | NICKEL - Aluminum (magnetic) Also known as: Ni-Al, Alumel™, Thermokanthal KN™, T2™, NiAl™ | 42 | 43 | 39 | 0 to +1100ºC | -180 to +1350ºC | Temperature Range Tolerance Value Temperature Range Tolerance Value | –40°C to +375°C ±1.5°C 375°C to 1000°C ±0.004 ⋅ |t| | –40°C to +333°C ±2.5°C 333°C to 1200°C ±0.0075 ⋅ |t| | T | COPPER | COPPER - NICKEL Also known as: Constantan, Advance™, Cupron™ | 46 | – | – | –185 to +300°C | –250 to +400°C | Temperature Range Tolerance Value Temperature Range Tolerance Value | –40°C to +125°C ±0.5°C 125°C to 350°C ±0.004⋅ |t| | –40°C to +133°C ±1.0°C 133°C to 350°C ±0.0075 ⋅ |t|

https://www.tc-inc.com/thermocouple/thermocouple-tolerances.html

tc.co.uk says source document is Thermocouple Colour Code Standards, as of 2026-08-19.

What is the Colour Code for a Type T Thermocouple? In the UK and Europe, the most widely used colour code for Type T thermocouple cable is to the international IEC 60584-3 standard which is as follows: Positive Leg = Brown, Negative Leg = White, Outer Sheath (Jacket) = Brown, Thermocouple Connector Colour = Brown

https://www.tc.co.uk/thermocouple-information/thermocouple-colour-code.html

Sources

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.