Reference Source

Wet chemical (e.g. K-type) · Hydrostatic test · NFPA 10 (2010 ed.)

For Wet chemical (e.g. K-type) · Hydrostatic test · NFPA 10 (2010 ed.), extinguishing agent / type is Wet chemical (e.g. K-type); service obligation is Hydrostatic test; interval is every 5 years; authority is NFPA 10 (2010 ed.); section is NFPA 10(10), Sec. 8.3.1 and Table 8.3.1, recorded from its source on 2026-08-19.

Extinguishing agent / type
Wet chemical (e.g. K-type) verified
Service obligation
Hydrostatic test our reading
Interval
every 5 years verified
Authority
NFPA 10 (2010 ed.) our reading
Section
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 verified
Sourcehealth.state.mn.us
Verified
Review by
DatasetFire extinguisher inspection, maintenance and hydrostatic test intervals by agent type

Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.

What the source says

Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years

health.state.mn.us, retrieved 2026-08-19

Source

Last verified against source: . Due for re-check by . This page as Markdown · OKF bundle · full dataset as JSON.