Carbon dioxide · Hydrostatic test
For Carbon dioxide · Hydrostatic test, extinguishing agent / type is Carbon dioxide; service obligation is Hydrostatic test; interval is every 5 years; nfpa 10 section is NFPA 10(10), Sec. 8.3.1 and Table 8.3.1, recorded from its source on 2026-08-19.
- Extinguishing agent / type
- Carbon dioxide verified
- Service obligation
- Hydrostatic test our reading
- Interval
- every 5 years verified
- NFPA 10 section
- NFPA 10(10), Sec. 8.3.1 and Table 8.3.1 verified
Values marked our reading are our classification of what the source says — the source does not print them in those words. The quote below is the evidence for each one; judge it yourself.
What the source says
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years
— health.state.mn.us, retrieved 2026-08-19
Source
- health.state.mn.ushttps://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf